No person should rely on the contents of the APCUPSD Manual ('the manual') without first obtaining advice from APC Technical Support. The manual is provided on the terms and understanding that: • the authors, contributors and editors are not responsible for the results of any actions taken on the basis of information in the manual, nor for any error in or omission from the manual; and • the authors, contributors and editors are not engaged in rendering technical or other advice or services.

The the authors, contributors and editors, expressly disclaim all and any liability and responsibility to any person, whether a reader of the manual or not, in respect of anything, and of the consequences of anything, done or omitted to be done by any such person in reliance, whether wholly or partially, on the whole or any part of the contents of the manual. Without limiting the generality of the above, no author, contributor or editor shall have any responsibility for any act or omission of any other author, contributor or editor. This is the manual for apcupsd, a daemon for communicating with UPSes (Uninterruptible Power Supplies) made by American Power Conversion Corporation (APC).

HxD is a carefully designed and fast hex editor which, additionally to raw disk editing and modifying of main memory (RAM), handles files of any size. The easy to use interface offers features such as searching and replacing, exporting, checksums/digests, insertion of byte patterns, a file shredder, concatenation or splitting of.

If you have an APC-made UPS, whether sold under the APC nameplate or OEMed (for example, the HP PowerTrust 2997A), and you want you get it working with a computer running Linux, Unix, or Windows, you are reading the right document. This manual is divided into parts which increase in technical depth as they go.

If you have just bought a state-of-the-art smart UPS with a USB or Ethernet interface, and you are running a current version of Red Hat or SUSE Linux, then apcupsd is very nearly plug-and-play and you will have to read only the. If your operating system is older, or if you have an old-fashioned serial-line UPS, you'll have to read about serial installation (see ). If you need more details about administration for unusual situations (such as a master/slave or multi-UPS setup) you'll need to read the sections on those topics as well. Finally, there are a number of technical reference sections which gives full details on things like configuration file directives and event-logging formats. You should begin by reading the Quick Start (see ) instructions.

Apcupsd is a complex piece of software, but most of its complexities are meant for dealing with older hardware and operating systems. On current hardware and software getting it running should not be very complicated. The following is a help guide to the steps needed to get apcupsd set up and running as painlessly as possible. • Check to see if apcupsd supports your UPS and cable (see ). • Check to see if apcupsd supports your operating system (see ). • Plan your configuration type (see ). If you have just one UPS and one computer, this is easy.

If you have more than one machine being served by the same UPS, or more than one UPS supplying power to computers that are on the same local network, you have more choices to make. • Figure out if you have one of the easy setups. If you have a USB UPS, and a supported operating system and you want to use one UPS with one computer, that's an easy setup. APC supplies the cable needed to talk with that UPS along with the UPS. All you need to do is check that your USB subsystem is working (see ); if so, you can go to the build and install step.

• If you have a UPS designed to communicate via SNMP over Ethernet, that is also a relatively easy installation. Details are provided in. • If you have a UPS that communicates via an RS232C serial interface and it is a SmartUPS, then things are relatively simple, otherwise, your life is about to get interesting. • If you have a vendor-supplied cable, find out what cable type you have by looking on the flat ends of the cable for a number, such as 940-0020A, stamped in the plastic. • If you don't have a vendor-supplied cable, or your type is not supported, you may have to build one yourself (see ). Here is hoping you are good with a soldering iron! • Now you are ready to read the Building and Installing (see ) section of the manual and follow those directions.

If you are installing from an RPM or some other form of binary package, this step will probably consist of executing a single command. • Tweak your /etc/apcupsd/apcupsd.conf file as necessary. Often it will not be. • Change the BIOS settings (see ) on your computer so that boots up every time it gets power. (This is not the default on most systems.) • To verify that your UPS is communicating with your computer and will do the right thing when the power goes out, read and follow the instructions in the Testing (see ) section.

• If you run into problems, check the apcupsd users' email list archive for similar problems. This is an excellent resource with answers to all sorts of questions. • If you still need help, send a message to the apcupsd users' email list () describing your problem, what version of apcupsd you are using, what operating system you are using, and anything else you think might be helpful. • Read the manual section on.

Apcupsd supports many UNIX-like operating systems as well as several variants of Windows. Due to lack of API standardization, USB support is not available on every platform. See below for details. In general it is recommended to obtain a prebuilt package for your platform.

Given how apcupsd must integrate into the shutdown mechanism of the operating system and the rate at which such mechanisms are changed by vendors, the platform ports in the apcupsd tree may become out of date. In some cases, binary packages are provided by the apcupsd team (RedHat, Mandriva, SuSE, Windows, Mac OS X).

For other platforms it is recommended to check your vendor's package repository and third party repositories for recent binary packages. Note that some vendors continue to distribute ancient versions of apcupsd with known defects. These packages should not be used. Apcupsd supports nearly every APC brand UPS model in existence and enough different cable types to connect to all of them. The UPSTYPE field is the value you will put in your /etc/apcupsd/apcupsd.conf file to tell apcupsd what type of UPS you have.

We'll describe the possible values here, because they're a good way to explain your UPS's single most important interface property: the kind of protocol it uses to talk with its computer. Apcsmart The 'apcsmart' protocol uses an RS232 serial connection to pass commands back and forth in a primitive language resembling modem-control codes. APC calls this language 'UPS-Link'. Originally introduced for Smart-UPS models (thus the name 'apcsmart'), this class of UPS is in decline, rapidly being replaced in APC's product line by USB and MODBUS UPSes. Usb A USB UPS speaks a universal well defined control language over a USB wire. Most of APC's lineup now uses this method as of late 2003, and it seems likely to completely take over in their low- and middle range. The most recent APC UPSes support only a limited set of data over the USB interface.

MODBUS (see below) is required in order to access the advanced data. Net This is the keyword to specify if you are using your UPS in Slave mode (i.e. The machine is not directly connected to the UPS, but to another machine which is), and it is connected to the Master via an ethernet connection. You must have apcupsd's Network Information Services NIS turned on for this mode to work. Snmp SNMP UPSes communicate via an Ethernet NIC and firmware that speaks Simple Network Management Protocol. Dumb A dumb or voltage-signaling UPS and its computer communicate through the control lines (not the data lines) on an RS232C serial connection. Not much can actually be conveyed this way other than an order to shut down.

Voltage-signaling UPSes are obsolete; you are unlikely to encounter one other than as legacy hardware. If you have a choice, we recommend you avoid simple signalling UPSes.

Pcnet PCNET is an alternative for SNMP available on APC's AP9617 family of smart slot modules. The protocol is much simpler and potentially more secure than SNMP.

Modbus MODBUS is the newest APC protocol and operates over RS232 serial links or USB. MODBUS is APC's replacement for the aging 'apcsmart' (aka UPS-Link) protocol. MODBUS is the only way to access detailed control and status information on newer (esp.

SMT series) UPSes. There are three major ways of running apcupsd on your system. The first is a standalone configuration where apcupsd controls a single UPS, which powers a single computer. This is the most common configuration. If you're working with just one machine and one UPS, skip the rest of this section.

Your choices become more interesting if you are running a small cluster or a big server farm. Under those circumstances, it may not be possible or even desirable to pair a UPS with every single machine.

Apcupsd supports some alternate arrangements. The second type of configuration is the NIS (Network Information Server) server and client. In this configuration, where one UPS powers several computers, a copy of apcupsd running one one computer will act as a server while the other(s) will act as network clients which poll the server for information about the UPS. Note that 'NIS' is not related to Sun's directory service also called 'NIS' or 'Yellow Pages'. The third configuration is where a single computer controls multiple UPSes. In this case, there are several instances of apcupsd on the same computer, each controlling a different UPS.

One instance of apcupsd will run in standalone mode, and the other instance will normally run in network mode. This type of configuration may be appropriate for large server farms that use one dedicated machine for monitoring and diagnostics Here is a diagram that summarizes the possibilities. Problem Linux 2.4 series kernels older than 2.4.22 (RH 9, RHEL 3) do not bind the USB device to the proper driver. This is evidenced by /proc/bus/usb/devices listing the UPS correctly but it will have 'driver=(none)' instead of 'driver=(hid)'. This affects RHEL3, among others. Workaround Upgrade linux kernel to 2.4.22 or higher.

Alternately, you apply the linux-2.4.20-killpower.patch and linux-2.4.20-USB-reject.patch patches to your kernel and rebuild it. These patches can be found in the examples/ directory in the apcupsd source distribution. Problem Mandrake 10.0 and 10.1 systems with high security mode enabled (running kernel-secure kernel) use static device nodes but still assign USB minor numbers dynamically. This is evidenced by hiddev0: USB HID v1.10 Device [.] instead of hiddev96. In dmesg log. Workaround Boot standard kernel instead of kernel-secure or disable CONFIG_USB_DYNAMIC_MINORS and rebuild kernel-secure. Problem USB driver linux-usb.c fails to compile, reporting errors about HID_MAX_USAGES undefined.

This is due to a defect in the linux kernel hiddev.h header file on 2.6.5 and higher kernels. Workaround Upgrade to apcupsd-3.10.14 or higher. These versions contain a workaround for the defect.

Problem On some systems such as Slackware 10.0, no USB devices will show up (see the next section). Workaround Add the following to rc.local mount -t usbdevfs none /proc/bus/usb Problem 2.6 kernels use udev and some distributions to not configure it to automatically create /dev/usb/hiddev?? As they should, causing apcupsd to fail to locate the UPS. Workaround Edit the file /etc/udev/rules.d/50-udev.rules, and add the following: KERNEL='hiddev*', NAME='usb/hiddev%n' More details are provided in the following section. To make sure that your USB subsystem can see the UPS, just do this from a shell prompt: cat /proc/bus/usb/devices This information is updated by the kernel whenever a device is plugged in or unplugged, irrespective of whether apcupsd is running or not. It contains details on all the USB devices in your system including hubs (internal and external), input devices, and UPSes.

Enable: ugen NetBSD (v4.0 and above) You can use apcupsd on single USB port without disabling the USB keyboard and mouse on other ports, though all other devices will be disabled on the port you pick for your UPS. First, decide which hub and port you wish to use. After building a properly configured kernel, reboot into that kernel and plug in your UPS USB cable. You should see a dmesg log message like the following: ugen0: American Power Conversion Back-UPS RS 1500 FW:8.g6.D USB FW:g6, rev 1.10/1.06, addr 2 Note that the ugen driver is called out. If you see uhid instead, it probably means you did not properly disable the uhid driver when you compiled your kernel or perhaps you're not running the new kernel. You can also check with ' usbdevs -d' to get a list of USB devices recognized by the system as well as the drivers they are associated with.

For example: # usbdevs -d addr 1: UHCI root hub, VIA uhub0 addr 2: Back-UPS RS 1500 FW:8.g6.D USB FW:g6, American Power Conversion ugen0. Apcupsd communicates with the UPS through the USB generic device, ugen. You may or may not need to manually make ugen device nodes in /dev, depending on what OS you are using.

FreeBSD No manual intervention needed. FreeBSD automatically creates the ugen nodes on demand. NetBSD By default, NetBSD only creates nodes for the first ugen device, ugen0.

Check usbdevs -d to see which device your UPS was bound to and then create the appropriate node by running ' cd /dev;./MAKEDEV ugenN', where ugenN is the ugen device name shown by usbdevs. It is probably a good idea to create several sets of ugen nodes in case you add more USB devices. OpenBSD Similar to NetBSD, OpenBSD creates nodes for ugen0 and ugen1. Check usbdevs -d to see which device your UPS was bound to and then create the appropriate node by running ' cd /dev;./MAKEDEV ugenN', where ugenN is the ugen device name shown by usbdevs. It is probably a good idea to create several sets of ugen nodes in case you add more USB devices. Some specific packages are necessary when building Apcupsd with USB support on Solaris.

You must install the SUNWlibusb and SUNWlibusbugen packages BEFORE attempting to build Apcupsd. These packages can be found on the Solaris installation CDROMs and should be installed with the pkgadd utility. You also should build using the gcc compiler and ccs make, not Sun's compiler. The appropriate make utility can be found in /usr/ccs/bin.

Gcc can be installed from packages included on the Solaris installation CDROMs. Configure and build Apcupsd normally, as described in. Be sure to include the --enable-usb flag to configure. After building, install Apcupsd as root using ' make install', then perform a reconfigure boot (' reboot -- -r').

During installation, Apcupsd will automatically configure your USB subsystem to attach APC USB devices to the ugen driver. This is a critical step and must be completed by a reconfigure boot.

Note that the USB config changes will be reversed if you remove Apcupsd using ' make uninstall'. After installing Apcupsd as described above and performing a reconfigure boot, plug in your UPS USB cable. Some specific packages are necessary when building Apcupsd with USB support on Darwin. You must install libusb-0.1.12 which can be obtained from MacPorts () (formerly DarwinPorts) or Fink () or downloaded and built by hand ().

You must not use libusb-1.x or higher (apcupsd does not support the new 1.0 APIs) nor any version earlier than 0.1.12 (earlier versions have a bug that apcupsd triggers). Generally that means you must use exactly 0.1.12. Note that Apcupsd is sensitive to the install location of libusb, so beware if you change it from the default. Apcupsd should be built using gcc, preferably from the XCode development tools.

Currently the maintainer is using gcc-4.0.1 from XCode 2.4. Other versions of gcc from other sources may also work. Configure and build Apcupsd normally, as described in. Be sure to include the --enable-usb flag to configure. After building, install Apcupsd as root using ' make install' and then reboot. During installation, Apcupsd will automatically install a simple dummy kext driver designed to prevent Apple's monitoring software from taking over the UPS.

It is necessary to reboot in order to activate the kext. Note that this kext will be automatically removed if you uninstall Apcupsd using ' make uninstall', allowing Apple's monitoring tool to once again access the UPS. In general it is recommended to obtain a prebuilt binary package for your platform. Given how apcupsd must integrate into the shutdown mechanism of the operating system and the rate at which such mechanisms are changed by vendors, the platform ports in the apcupsd tree may become out of date. In some cases, binary packages are provided by the apcupsd team (RedHat, Mandriva, SuSE, Windows, Mac OS X). For other platforms it is recommended to check your vendor's package repository and third party repositories for recent binary packages before resorting to building apcupsd from scratch.

Note that some vendors continue to distribute ancient versions of apcupsd with known defects. These packages should not be used. For systems based on RPM packages, such as Red Hat and SuSE, apcupsd is available in binary RPM format. This is the simplest way to install. If you have no previous version of apcupsd on your machine and are creating a standalone configuration, simply install the RPM with a normal ' rpm -ihv' command. You're done, and can now skip the rest of this chapter and go straight to tweaking your run-time configuration file. (see ) If you have a previous installation, you can upgrade with a normal ' rpm -Uhv', but this may not upgrade the halt script.

It may be better to do the upgrade as a remove ' rpm -e' followed by a fresh install ' rpm -ihv'. After installation of the binary RPM, please verify carefully that /etc/rc.d/init.d/halt was properly updated and contains new script lines flagged with ***APCUPSD***. Since there is no standard location for cgi-bin, the rpm will place the binary CGI programs in the directory /etc/apcupsd/cgi. To actually use them, you must copy or move them to your actual cgi-bin directory, which on many systems is located in /home/httpd/cgi-bin. Installation from source might have to be be done different ways depending on what system you are running.

The basic procedure involves getting a source distribution, running the configuration, rebuilding, and installing. For building the system, we suggest that you run the configure and make processes as your normal UNIX user ID.

The ' make install' must be run as root. But if your normal ID has an environment setup for using the C compiler, it's simpler to do that than to set up root to have the correct environment.

Apcupsd requires gcc and g++ compilers as well as GNU make. Other compilers or BSD make will not work. Port Forward Network Utilities Serial. GNU make is sometimes installed as gmake. The configure script will check for this and will inform you of what command to use to invoke GNU make. The basic installation from a tar source file is rather simple: • Unpack the source code from its tar archive. • Go into the directory containing the source code. • Run './configure' (with appropriate options as described below) • ' make' or ' gmake' as instructed by configure • ' su' (i.e.

Become root) • Stop any running instance of apcupsd. The command to do this will look like ' system-dependent-path/apcupsd stop' • uninstall any old apcupsd This is important since the default install locations may have changed. • ' make install' or ' gmake install' • edit your /etc/apcupsd/apcupsd.conf file if necessary • ensure that your halt script is properly updated • Start the new apcupsd with: ' system-dependent-path/apcupsd start' If all goes well, the './configure' will correctly determine which operating system you are running and configure the source code appropriately. Configure currently recognizes the systems listed below in the section of this chapter and adapts the configuration appropriately.

Check that the configuration report printed at the end of the configure process corresponds to your choice of directories, options, and that it has correctly detected your operating system. If not, redo the configure with the appropriate options until your configuration is correct. Please note that a number of the configure options preset apcupsd.conf directive values in an attempt to automatically adapt apcupsd as best possible to your system. You can change the values in apcupsd.conf at a later time without redoing the configuration process by simply editing the apcupsd.conf file. Other configuration options can be used to set up the installation of HTML documentation and optional modules, notably the CGI interface that enables the UPS state to be queried via the Web.

You will find a complete reference later in this chapter. In general, you will probably want to supply a more elaborate configure statement to ensure that the modules you want are built and that everything is placed into the correct directories. On Red Hat, a fairly typical configuration command would look like the following: CFLAGS='-g -O2' LDFLAGS='-g'./configure --enable-usb --with-upstype=usb --with-upscable=usb --prefix=/usr --sbindir=/sbin --with-cgi-bin=/var/www/cgi-bin --enable-cgi --with-log-dir=/etc/apcupsd By default, ' make install' will install the executable files in /sbin, the manuals in /usr/man, and the configuration and script files in /etc/apcupsd. In addition, if your system is recognized, certain files such as the startup script and the system halt script will be placed in appropriate system directories (usually subdirectories of /etc/rc.d).

All the available configure options can be printed by entering:./configure --help When specifying options for './configure', if in doubt, don't put anything, since normally the configuration process will determine the proper settings for your system. The advantage of these options is that it permits you to customize your version of apcupsd. If you save the './configure' command that you use to create apcupsd, you can quickly reset the same customization in the next version of apcupsd by simply re-using the same command. The following command line options are available for configure to customize your installation. --prefix= path This defines the directory for the non-executable files such as the manuals.

The default is /usr. --sbindir= path This defines the directory for the executable files such as apcupsd. The default is /sbin.

You may be tempted to place the executable files in /usr/sbin or /usr/local/sbin. Please use caution here as these directories may be unmounted during a shutdown and thus may prevent the halt script from calling apcupsd to turn off the UPS power.

Though your data will be protected, in this case, your system will probably not be automatically rebooted when the power returns --enable-cgi This enables the building of the CGI programs that permit Web browser access to apcupsd data. This option is not necessary for the proper execution of apcupsd.

--with-cgi-bin= path The with-cgi-bin configuration option allows you to define the directory where the CGI programs will be installed. The default is /etc/apcupsd, which is probably not what you want. --enable-apcsmart Turns on generation of the APC Smart driver (default). --enable-dumb Turns on generation of the dumb signalling driver code (default). --enable-usb Turns on generation of the USB driver code. By default this is disabled.

--enable-net Turns on generation of the NIS network driver for slaves. For each slave, this is the only driver needed. This driver works by reading the information from the the configured master using the NIS (Network Information Services) interface. --enable-snmp Turns on generation of the SNMP driver. This driver accesses the UPS over the network using SNMP.

This is compatible only with UPSes equipped with an SNMP or Web/SNMP management card. By default this is enabled. --enable-pcnet Turns on generation of the PCNET (PowerChute Network Shutdown) driver. This driver accesses the UPS over the network using APC's custom protocol. This driver can be used as an alternative to SNMP for UPSes equipped with a modern Web/SNMP management card. --enable-modbus Turns on generation of the MODBUS/RS232 driver (default) --enable-modbus-usb Turns on generation of the MODBUS/USB driver --enable-test This turns on a test driver that is used only for debugging.

By default it is disabled. --enable-gapcmon This option enables building the GTK GUI front-end for apcupsd. Building this package requires numerous GNOME libraries. The default is disabled. --enable-apcagent This option enables building the apcagent menubar application on Mac OS X platforms. The default is disabled. --with-libwrap= path, --with-libwrap This option when enabled causes apcupsd to be built with the TCP WRAPPER library for enhanced security.

In most cases, the path is optional since configure will determine where the libraries are on most systems. --with-nologin= path This option allows you to specify where apcupsd will create the nologin file when logins are prohibited. The default is /etc --with-pid-dir= path This option allows you to specify where apcupsd will create the process id (PID) file to prevent multiple copies from running.

The default is system dependent but usually /var/run. --with-log-dir= path This option allows you to specify where apcupsd will create the EVENTS and STATUS log files. The default is /etc/apcupsd. This option simply sets the default of the appropriate path in the apcupsd.conf file, which can be changed at any later time. --with-lock-dir= path This option allows you to specify where apcupsd will create the serial port lock file. The default is system-dependent but usually /var/lock.

This option simply sets the appropriate path in the apcupsd.conf file, which can be changed at any later time. --with-pwrfail-dir= path This option allows you to specify where apcupsd will create the powerfail file when a power failure occurs. The default is system dependent but usually /etc. --with-serial-dev= device-name This option allows you to specify where apcupsd will look for the serial device that talks to the UPS. The default is system dependent, but often /dev/ttyS0. This option simply sets the appropriate device name in the apcupsd.conf file, which can be changed at any later time.

--with-nis-port= port This option allows you to specify what port apcupsd will use for the Network Information Server (the CGI programs). The default is system dependent but usually 3551 because that port has been officially assigned to apcupsd by the IANA. This option simply sets the appropriate port in the apcupsd.conf file, which can be changed at any later time. --with-nisip= ip-address This option allows you to specify the value that will be placed on then NISIP directive in the configuration file. The default is 0.0.0.0. No checking is done on the value entered, so you must ensure that it is a valid IP address. --with-net-port= port This option allows you to specify what port apcupsd will use for Master and Slave communications.

The default is system dependent but usually 6666. This option simply sets the appropriate port in the apcupsd.conf file, which can be changed at any later time. --with-upstype= type This option allows you to specify the type of UPS that will be connected to your computer.

The default is: smartups. This option simply sets the appropriate UPS type in the apcupsd.conf file, which can be changed at any later time. --with-upscable= cable This option allows you to specify what cable you are using to connect to the UPS. The default is: smart. This option simply sets the appropriate UPS cable in the apcupsd.conf file, which can be changed at any later time. --disable-install-distdir This option modifies the apcupsd Makefiles disable installation of the distribution (platform) directory. Generally, this used to do a full installation of apcupsd except the final modification of the operating system files (normally /etc/rc.d/halt, etc.).

This is useful if your operating system is not directly supported by apcupsd or if you want to run two copies of apcupsd on the same system. This option can also be used by those of you who prefer to manually reboot your system after a power failure or who do not want to modify your system halt files. Some systems require unusual options for compilation or linking that the './configure' script does not know about.

You can specify initial values for variables by setting them in the environment. Using a Bourne-compatible shell, you can do that on the command line like this: CFLAGS='-O2 -Wall' LDFLAGS=./configure Or on systems that have the env program, you can do it like this: env CPPFLAGS=-I/usr/local/include LDFLAGS=-s./configure Or for example on the Sun Solaris system, you can use: setenv CFLAGS -O2 setenv LDFLAGS -O./configure You can get a listing of all available options by doing:./configure --help or simply see the previous section of this manual. With the exception of Linux SUSE and Linux Red Hat systems used by the developers, we rely on users to help create installation scripts and instructions as well as to test that apcupsd runs correctly on their system. As you can imagine, most of these people are system administrators rather than developers so they are very busy and don't always have time to test the latest releases. With that in mind, we believe that you will find that a lot of very valuable work has been already done to make your installation much easier (and probably totally automatic). Below, you will find a list of operating systems for which we have received installation files: • Debian (see ) • FreeBSD (see ) • HPUX (see ) • NetBSD (see ) • Mac OS X Darwin (see ) • OpenBSD (see ) • Red Hat (see ) • Slackware (see ) • SUSE (see ) • Solaris (see ) • unknown (see ) • Win32 (see ). This port is complete and is being used by several users.

You will need to install and use GNU make (aka gmake) instead of the BSD make supplied with the system. On the FreeBSD OS, there is no known way for a user program to get control when all the disks are synced. This is needed for apcupsd to be able to issue the killpower command to the UPS so that the UPS shuts off the power. To accomplish the same thing on FreeBSD systems, make sure you have a SmartUPS and that your UPS shutdown grace period is set sufficiently long so that you system will power down (usually 2 minutes), the use the --kill-on-powerfail option on the apcupsd command line. Please read this before attempting to compile or install the beta software. It contains important information that will make your efforts easier.

Before running './configure', please be sure that you do not have /usr/ucb on your path. This may cause the configure to choose the wrong shutdown program. If configure detects that /usr/usb is on your path, it will print a warning message. Please follow the advice to avoid shutdown problems.

Your normal UNIX user ID must own the source tree directories, and you must have the normal development tools in your path. This includes make, the compiler, the M4 preprocessor, the linker, and ar or ranlib. If the user you are logged in as can compile and link a C program from a source file, then you have all the required tools available.

You will want to install the executables in a directory that remains mounted during the shutdown. Solaris will unmount almost everything except the root directories.

Since the ability to power the UPS off requires access to the executable programs, they need to be in a directory that will never be unmounted. And since they should also be in a directory that normal users cannot get into, /sbin is the default. However, please be aware that if you want to follow Sun's filesystem conventions you would use the following:./configure --prefix=/opt/apcupsd --sbindir=/etc/opt/apcupsd/sbin --sysconfdir=/etc/opt/apcupsd --with-cgi-bin=/opt/apcupsd/cgi-bin The way to setup the /sbin directory as the executables directory is to pass configure the --sbindir=/sbin option. No other arguments should be required, and your setup and platform should be detected automatically by configure. Once you have run configure, you will need to do a ' gmake'. Once the make has completed with no errors, you must su to root to complete the install. After the su, you may not have a path to the make program anymore.

In that case, you should do the ' gmake install' step as: gmake install Once the install completes, you must edit the /sbin/rc0 script as detailed below, then exit from the su'ed shell. In order to support unattended operation and shutdown during a power failure, it's important that the UPS remove power after the shutdown completes. This allows the unattended UPS to reboot the system when power returns by re-powering the system. Of course, you need autoboot enabled for your system to do this, but all Solaris systems have this by default.

If you have disabled this on your system, please re-enable it. To get the UPS to remove power from the system at the correct time during shutdown, i.e., after the disks have done their final sync, we need to modify a system script. This script is /sbin/rc0. We do not have access to every version of Solaris, but we believe this file will be almost identical on every version. Please let us know if this is not true.

At the very end of the /sbin/rc0 script, you should find lines just like the following: # unmount file systems. /usr, /var and /var/adm are not unmounted by umountall # because they are mounted by rcS (for single user mode) rather than # mountall. # If this is changed, mountall, umountall and rcS should also change.

/sbin/umountall /sbin/umount /var/adm >/dev/null 2>&1 /sbin/umount /var >/dev/null 2>&1 /sbin/umount /usr >/dev/null 2>&1 echo 'The system is down.' We need to insert the following lines just before the last 'echo': #see if this is a powerfail situation if [ -f /etc/apcupsd/powerfail ]; then echo echo 'APCUPSD will power off the UPS' echo /etc/apcupsd/apccontrol killpower echo echo 'Please ensure that the UPS has powered off before rebooting' echo 'Otherwise, the UPS may cut the power during the reboot!!!'

Echo fi We have included these lines in a file called rc0.solaris in the distributions/sun subdirectory of the source tree. You can cut and paste them into the /sbin/rc0 file at the correct place, or yank and put them using vi or any other editor. Note that you must be root to edit this file.

You must be absolutely sure you have them in the right place. If your /sbin/rc0 file does not look like the lines shown above, do not modify the file.

Instead, email a copy of the file to the maintainers, and we will attempt to figure out what you should do. If you mess up this file, the system will not shut down cleanly, and you could lose data. Don't take the chance. You will then need to make the normal changes to the /etc/apcupsd/apcupsd.conf file.

This file contains the configuration settings for the package. It is important that you set the values to match your UPS model and cable type, and the serial port that you have attached the UPS to.

People have used both /dev/ttya and /dev/ttyb with no problems. You should be sure that logins are disabled on the port you are going to use, otherwise you will not be able to communicate with the UPS. If you are not sure that logins are disabled for the port, run the 'admintool' program as root, and disable the port. The 'admintool' program is a GUI administration program, and required that you are running CDE, OpenWindows, or another XWindows program such as KDE.

Solaris probes the serial ports during boot, and during this process, it toggles some handshaking lines used by dumb UPSes. As a result, particularly for simple signalling 'dumb' UPSes it seems to kick it into a mode that makes the UPS think it's either in a calibration run, or some self-test mode. Since at this point we are really not communicating with the UPS, it's pretty hard to tell what happened.

But it's easy to prevent this, and you should. Disconnect the UPS, and boot the system. When you get to a login prompt, log in as root.

Type the following command: eeprom com1-noprobe=true or eeprom com2-noprobe=true depending on which com port your UPS is attached to. Then sync and shutdown the system normally, reattach the UPS, and reboot. This should solve the problem.

However, we have some reports that recent versions of Solaris (7 & 8) appear to have removed this eeprom option and there seems to be no way to suppress the serial port probing during boot. At this point, you should have a complete installation. The daemon will load automatically at the next boot. Watch for any error messages during boot, and check the event logs in /etc/apcupsd. If everything looks OK, you can try testing the package by removing power from the UPS.

If you have a voltage-signalling UPS, please run the first power tests with your computer plugged into the wall rather than into the UPS. This is because dumb serial-port UPSes have a tendency to power off if your configuration or cable are not correct. As a user, your input is very helpful in solving problems with the package, and providing suggestions and future directions for the development of the package. We are striving to provide a useful package that works across all platforms, and welcome your feedback. Once you have installed apcupsd, either from a binary package or by building from source, your next step should be to inspect your /etc/apcupsd/apcupsd.conf file to make sure it is valid. You can read the complete reference on configuration directives (), but if you are setting up a normal standalone configuration you should only need to check (and possibly fix) the first three items listed below.

Your UPSTYPE should be the UPS's protocol type: dumb, apcsmart, usb, net, pcnet, or snmp. Your UPSCABLE should be the type of cable you are using. DEVICE should be set to the path of the device node (usually in /dev) to use to communicate with the UPS. This is used primarily for serial port connections. If you have a USB device, it is better not to specify a DEVICE directive by leaving it black or commenting it out.

Apcupsd will automatically search for your device in the standard places. If you specify a DEVICE, it should be the name of the device that apcupsd is to use to communicate with the UPS. If the first time you execute apcupsd, you get a message to the effect that the Apcupsd USB driver is missing, it means that you most likely forgot to put --enable-usb on your './configure' command line. The chapter of this manual provides the essential characteristics of each main type of configuration file. After those elements are correct, apcupsd should run, and then it is only a matter of customization of your setup.

The final consideration for a automatic reboot after a full power down is to ensure that your computer will automatically reboot when the power is restored. This is not the normal behavior of most computers as shipped from the factory. Normally after the power is cut and restored, you must explicitly press a button for the power to actually be turned on.

You can test your computer by powering it down; shutting off the power (pull the plug); then plugging the cord back in. If your computer immediately starts up, good. There is nothing more to do. If your computer does not start up, manually turn on the power (by pressing the power on button) and enter your computer's SETUP program (often by pressing DEL during the power up sequence; sometimes by pressing F10).

You must then find and change the appropriate configuration parameter to permit instant power on. Normally, this is located under the BOOT menu item, and will be called something such as Restore on AC/Power Loss or Full-On. The exact words will vary according to the ROM BIOS provider.

Generally you will have three options: Last State, Power On, and Power Off. Although Last State should normally work, we recommend setting your computers to Power On. This means that whenever the power is applied they are on. The only way to shut them off is to pull the plug or to have a special program that powers them off (/sbin/poweroff on Linux systems). If after making all the changes suggested above, you cannot get your computer to automatically reboot, you might examine your halt script (/etc/rc.d/init.d/halt in the case of Red Hat Linux) and see if the final line that performs the halt or reboot contains the -p option for powering down the computer.

It should not with the logic used by apcupsd, but if it does, the -p option could cause your computer to power off while the UPS is still suppling power (i.e. Before the UPS kills the power). Depending on the setting of your BIOS, it may prevent your computer from restarting when the power returns. As already mentioned, this should not apply, but in case of problems it is worth a try.

The simplest way to invoke apcupsd is from the command line by entering: /sbin/apcupsd To do so, you must be root. However, normally, you will want apcupsd started automatically when your system boots. On some systems with installation support (e.g. SUSE and Red Hat), the installation procedure will create a script file that you will be automatically invoked when your system reboots. On other systems, you will have to invoke apcupsd from your rc.local script. On Red Hat systems, this script file that automatically invokes apcupsd on system start and stops is /etc/rc.d/init.d/apcupsd To start apcupsd manually (as you will probably do immediately following the installation), enter the following: /etc/rc.d/init.d/apcupsd start To understand how this file is automatically invoked at system startup and shutdown, see the man pages for chkconfig(8). On SUSE systems, the script file that automatically invokes apcupsd on system start and stops is /etc/rc.d/apcupsd.

To start apcupsd manually (as you will probably do immediately following the installation), enter the following: /etc/rc.d/apcupsd start Normally, when properly installed, apcupsd will be started and stopped automatically by your system. Unfortunately, the details are different for each system. Below, we give the commands for selected systems. Alternatively, there are simple stopapcupsd and startapcupsd scripts in the examples directory, or you can modify one of the scripts in the distributions directory to meet your needs. To stop apcupsd you can do the following: On Red Hat systems: /etc/rc.d/init.d/apcupsd stop On SUSE systems: /etc/rc.d/apcupsd stop Please see the chapter for more details on insuring that apcupsd is running properly. If you have a USB UPS, the essential elements of your apcupsd.conf file should look like the following: ## apcupsd.conf v1.1 ## UPSCABLE usb UPSTYPE usb DEVICE LOCKFILE /var/lock UPSCLASS standalone UPSMODE disable Notice that we have not specified a device.

In doing so, apcupsd will try all the well known USB ports. We strongly recommend you use this (empty device address) form unless you have a good reason to do otherwise. Please use the explicit specifications of a device only if you know exactly what you are doing. In general, it is much easier to let apcupsd find the device itself. Please see for detailed help on setting up your system to work with a USB UPS. If you have a simple signaling or dumb UPS such as a BackUPS, you will need to know exactly what cable you have and specify it on the UPSCABLE directive.

Please see the list of UPSes versus cables in the beginning of this document for more information. The cable number is normally stamped in the plastic at one end of the cable. If you specify the wrong cable, it is very likely that at the first power failure, your computer will be immediately shutdown. This is an unfortunate consequence of the dumb signaling mode. To avoid this, first replace /etc/apcupsd/apccontrol with safe.apccontrol found in the examples directory, then test until everything works correctly. Once you have the correct cable, be sure to remember to reinstall the correct apccontrol file and test that your computer is correctly shutdown during a power failure.

## apcupsd.conf v1.1 ## UPSCABLE (number of cable you have) UPSTYPE dumb DEVICE /dev/ttyS0 LOCKFILE /var/lock UPSCLASS standalone UPSMODE disable If your cable does not have low battery detection, as is the case with some older models, you will also need to define TIMEOUT nnn where you set nn to be the number of seconds on a power failure after which a shutdown is effected. Normally you would have many more configuration directives to completely customize your installation, but this example shows you the minimum required. NIS (Network Information Server) mode allows for communication between instances of apcupsd running on different hosts. Only one of those hosts, the server, needs to talk to the UPS directly. The others, clients, obtain information about the state of the UPS by querying the server.

NIS is not related to Sun's NIS/YP services. NIS clients and servers require that apcupsd be compiled with the Net Driver --enable-net. This is typically enabled by default. The NIS server is connected to the UPS and should be configured exactly as a standalone configuration, but with NETSERVER on. In all other respects, the server should be configured in standalone mode. You may also set the NIS server specific options NISIP to restrict which IP address of the server which apcupsd listens on. The default, 0.0.0.0, means to list on all of the server host's IP addresses; NISPORT (default 3551) to set which TCP port the server listens on; and EVENTSFILE and EVENTSFILEMAX to provide information about the last few events to clients.

You may also need to modify your firewall rules on the server's host to allow traffic to the NISPORT. For the NIS client computer, you will have a configuration that looks something like what follows. What is important is that you get the information from an UPSCABLE ether with UPSTYPE net over the network and you must specify the address of a NIS server using DEVICE. The client apcupsd will then poll the NIS server specified in DEVICE every POLLTIME seconds (formerly NETTIME).

## apcupsd.conf v1.1 ## UPSCABLE ether UPSTYPE net LOCKFILE /var/lock DEVICE server-network-address:3551 UPSCLASS standalone UPSMODE disable POLLTIME 10 The DEVICE is set to server-address:port, where server-address is the fully qualified domain name or IP address of the apcupsd NIS server, and port is the NISPORT that the server is listening on. The default is 3551, but older versions of apcupsd used port 7000.

If you set POLLTIME too large, your client may not see the change in state of the NIS server before the server has shutdown. Normally, you have at least 30 seconds of grace time between the time the NIS server decides to shutdown and the time it no longer responds. Your slave must poll during this interval. Any client run using the Net driver will shutdown when its own timers expire or when the NIS server shuts down, whichever occurs first.

This means that if you want the slave to shutdown before the server, you need only set BATTERYLEVEL, MINUTES or TIMEOUT on the client for a faster shutdown than the values defined on the NIS server. This can often be useful if the slave is less important than the master and you wish to reduce battery power consumption so that the master can remain up longer during a power outage. NIS clients work principally by reading the STATFLAG record that is sent by the NIS server (present in the output of apcaccess). The low 16 bits are the standard APC status flag, and the upper 16 bits represent the internal state of apcupsd, so the slave can see when the power fails and know when to shutdown.

It would be possible to have a client also work as a server, but that would increase the delay of information getting from the UPS to the secondary client. The difference between the NIS mode and the removed master/slave mode is that the NIS server has no explicit knowledge of the slaves. The NIS server makes its information available via the net (NIS), and the NIS slaves read it.

When the NIS server is going to shutdown, it makes the information available to any NIS slave that polls it, but the NIS server does not explicitly call each NIS slave as is the case in the Master/Slave networking described several sections above. Think of the difference as push (Master/Slave) vs. Pull (NIS-based). In the case of M/S, the master makes all the shutdown decisions and notifies the slaves when they are to shut down or when some other interesting event happens.

The slaves just do whatever the master says, whenever the master says to. On the other hand, with the NIS-based network config you basically 'publish' the UPS status from one server and then your clients view that status and make their own decisions. As of 3.14, Apcupsd supports the PowerChute Network Shutdown protocol. This is an alternative to SNMP for use with APC's AP9617 family of network smartslot modules.

Note that the older AP9606 modules do not support PCNET. To enable PCNET support, configure with the --enable-pcnet flag.

This is typically enabled by default. The required apcupsd.conf settings are straightforward: ## apcupsd.conf v1.1 ## UPSCABLE ether UPSTYPE pcnet LOCKFILE /var/lock DEVICE ipaddr:user:passphrase UPSCLASS standalone UPSMODE disable The DEVICE setting specifies the IP address of the UPS as well as the username and authentication passphrase to use. Note that the username and passphrase are not the Web/SNMP login credentials. They are separate settings. The default username on a new card is ' apc' and the default passphrase is ' admin user phrase'.

To change the passphrase, log in to the Web UI and go to the UPS tab, then to PowerChute ->Configuration. (This assumes firmware v3.3.1. Other versions may place the setting elsewhere.) The password must be a minimum of 15 characters long. The web UI will silently ignore shorter passwords and does not give an error message. There is no apparent way to change the username. Note that you may leave DEVICE blank and Apcupsd will accept information from any PCNET UPS on the network, however it will be very insecure since an attacker could easily send packets crafted to cause your server to shut down. Using the ipaddr, user, and passphrase will prevent this behavior.

You may need to take steps to ensure networking stays active during your OS's shutdown sequence in order for the PCNET driver to power off the UPS (the so-called 'killpower' operation). On a Linux distro, you can use commands such as. Chkconfig --level 0 network on chkconfig --level 0 iptables on.to make sure networking stays up. MODBUS is APC's replacement for the aging 'apcsmart' (aka UPS-Link) protocol. It is recommended for modern (ex: SMT series) Smart-UPS models. As of 3.14.11, apcupsd supports the MODBUS protocol over RS232 serial interfaces. As of 3.14.13, apcupsd supports the MODBUS protocol over USB.

Not all APC UPSes support MODBUS. New 2013 year Smart-UPS models are likely to support it out-of-the-box and firmware updates are available for some older models. APC/Schneider tech support is your best point of contact for determining if a certain model will support MODBUS. That said, APC knowledge base article FA164737 indicates MODBUS support is available for the majority of the SMC, SMT, and SMX model lines. The required apcupsd.conf settings for MODBUS are straightforward.

For MODBUS serial RS232: ## apcupsd.conf v1.1 ## UPSCABLE smart UPSTYPE modbus DEVICE /dev/ttyS0 LOCKFILE /var/lock UPSCLASS standalone UPSMODE disable The DEVICE setting identifies the serial port to which the UPS is connected. This can take the form of COM1, etc. On Windows or /dev/XXX on UNIX systems. You should use the APC-supplied serial cable (P/N 940-0625A) that ships with the UPS.

Other 'smart' type cables may work, but only 940-0625A has been formally tested at this time. For MODBUS USB: ## apcupsd.conf v1.1 ## UPSCABLE usb UPSTYPE modbus DEVICE LOCKFILE /var/lock UPSCLASS standalone UPSMODE disable The DEVICE setting can be left blank or, optionally, set to the serial number of the UPS. If DEVICE is blank, apcupsd will attach to the first APC UPS it finds, otherwise it will attach to the specific UPS identified by the serial number.

Note that most UPSes ship with MODBUS support disabled by default. You must use the UPS's front panel menu to enable MODBUS protocol support before apcupsd will be able to communicate with the UPS. You may need to enable the 'Advanced' menu option before the MODBUS protocol option will be visible. After you start apcupsd, execute the following command: ps fax or the equivalent for your system. You should see something similar to the following output. S 0:00 /sbin/apcupsd -f /etc/apcupsd/apcupsd.conf 841?

S 0:00 _ /sbin/apcupsd -f /etc/apcupsd/apcupsd.conf 842? S 0:00 _ /sbin/apcupsd -f /etc/apcupsd/apcupsd.conf This indicates that apcupsd is up and running and has started the two standard threads in addition to the main thread. If you see only one instance of apcupsd running, don't worry about it as this is normal on most non-Linux systems, and on Linux 2.6.x kernels. If you do not find that apcupsd is in the above list, the most likely problem is a configuration file glitch. If no messages were printed, you should check your system log (normally /var/log/messages) where you will find one or messages indicating the nature of the problem. This test consists of running apcaccess to see if apcupsd is properly updating its internal variables.

Please note that you must enable the apcupsd Network Information Server in your configuration file for apcaccess to work. This is done by setting: NETSERVER on NISPORT 3551 in your apcupsd.conf file. At this point, you should ensure that apcupsd is handling the connection to the UPS correctly. This test assumes you have a UPS that speaks apcsmart protocol, over either USB or a serial port. If you have an old-style voltage-signaling UPS, please skip to the next section ().

When apcupsd detects a problem, it generates an EVENT, which consists of sending a message to the system log then invoking the apccontrol script (normally in /etc/acpupsd/apccontrol) to handle the event. In order to create an event, remove the serial port plug from the back of your computer or from the back of the UPS. Within 6 seconds, apcupsd should detect the lack of serial port communications and broadcast a wall message indicating that the serial port communications was lost: Warning communications lost with UPS lost. At the same time, it sends the same message to the system log and to the temporary EVENTS file ( /etc/apcupsd/apcupsd.events).

Plug the serial port plug back into your computer, and within about 12 seconds, apcupsd should reestablish communications and broadcast and log the following message: Communications with UPS restored. If these messages are logged but not broadcast, either you have your mesg permission set to no (see ' man wall' or ' man mesg'), or there is a problem with apccontrol. If you are running a window manager such as GNOME and don't have a console window open, you may not receive the wall messages. However, you should find them in your system log file (normally /var/log/messages) and in the temporary EVENTS file, /etc/apcupsd/apcupsd.events. For example, to observe these events in the temporary EVENTS file, you might do a tail -f /etc/apcupsd/apcupsd.events Note, if you have installed from the RPM, the proper events file may be /var/log/apcupsd.events. You can find the actual filename by checking your apcupsd.conf file before running the test.

If you do not observe these messages, you should correct this problem before proceeding with additional tests. At this point, you should verify that in the event of a power fail apcupsd properly calls apccontrol. This test is appropriate for all models of UPSes (smart or dumb). To avoid the possibility that apcupsd might shut down your system, locate where apccontrol resides on your system (normally, /etc/apcupsd/apccontrol. Move this script to another location e.g. Apccontrol.save and replace it with the script found in examples/safe.apccontrol.

When that is done, ensure that your UPS battery is fully charged and that you have at least 5 minutes of remaining runtime on the batteries. This can be done by examining the values of the BATTCHG and TIMELEFT variables in the printout of ' apcaccess status'. Athough this should not be necessary, as an extra precaution, you can shutdown your machine, remove the plug from the UPS you are testing, and plug your machine into another UPS or directly into the wall.

Doing so, will ensure that the UPS doesn't cut the power to your machine at a bad time. Remember at the end of the testing to plug your machine back into the UPS. You can also minimize the risk from an unexpected shutdown by using a journaling filesystem such as Linux's EXT3. All modern disk drives park themselves safely when they power down, rather than ploughing up oxide on your disk's recording surface. Thus, unexpected power less has to hit very narrow timing windows in order to trash an EXT3 transaction. To begin the test, pull the power plug from the UPS.

The first time that you do this, psychologically it won't be easy, but after you have pulled the plug a few times, you may even come to enjoy it. If all goes well, apcupsd should detect the power failure and print several warning messages. The first should appear after 5 to 6 seconds and read: Warning power loss detected.

Then generally 6 seconds later, apcupsd is sure that it isn't a transient effect, so it sends: Power failure. Running on UPS batteries. After a few more seconds (total around 15 seconds), plug the power cord back in and ensure that apcupsd is aware that the power has returned. It should print: Power has returned. If you do not observe the above messages, please correct the situation before proceeding.

The most likely cause of problems are: • apcupsd doesn't recognize the power failure because the configuration directives are not correct. • The file /etc/apcupsd/apccontrol doesn't exist or is not marked as executable. To complete the testing, you should do a power fail shutdown of your system. This test is applicable to all UPS models. Please do a backup of your system or take other precautions before attempting this to avoid the possibility of lost data due to a problem (I have been through this at least 10 times and never once had problems, but we all know that someday something will go wrong). Before proceeding, please ensure that your halt script or the equivalent has been properly updated by the install process to contain the logic to call apcupsd --killpower or apccontrol killpower when it detects a power failure situation (the presence of a /etc/powerfail file). See the section of this manual, or the README files for additional details about the halt modifications necessary.

When you are ready to do the test, either simply pull the plug and wait for the batteries to become exhausted, or set the TIMEOUT configuration directive to something like 60 so that the system will shutdown before the batteries are exhausted. We recommend doing the full shutdown without using TIMEOUT to correctly simulate a real power failure, but the choice is yours (I did it once here, but now use TIMEOUT 30). If all goes well, your system should be shutdown before the batteries are completely exhausted and the UPS should be powered off by apcupsd. Please be aware that if you do the full power down, you must ensure that your UPS is totally powered off. Otherwise, it may have been given the command to power off, but due to a long grace period it is still waiting. If you were to reboot your computer during the grace period, the UPS could then suddenly turn off the power (this happened to me). To avoid this problem, always wait for your UPS to power itself off, or power if off manually before restarting your computer.

On my system, the UPS is configured as at the factory to have a 180 second grace period before shutting off the power. During this type of testing, 180 seconds seems like an eternity, so please take care to either wait or manually power off your UPS. To determine what grace period is programmed into your UPS EEPROM, run ' apcaccess eprom' and look at the 'Shutdown grace delay'. If you experienced so problems with the above testing procedures, or if you are porting apcupsd to another system, or you are simply curious, you may want to know exactly what is going on during the shutdown process. If so, please see the section of this manual.

Apctest is a program that allows you to talk directly to your UPS and run certain low-level tests, adjust various settings such as the battery installation date and alarm behavior, and perform a battery runtime calibration. Here we describe how to use it for a SmartUPS utilizing the apcsmart driver and RS232 serial connection. The menus and options for USB, MODBUS, and simple signaling UPSes are different but mostly self-explanatory. Shutdown apcupsd if it is running.

This is important. Only one program can communicate with the UPS at a time and if apcupsd is running, apctest will fail to contact the UPS. Run apctest by invoking it with no arguments. It will read your installed apcupsd.conf configuration (so it knows where to find the UPS) and then it will present you with the following output: 2003-07-07 11:19:21 apctest 3.10.6 (07 July 2003) redhat Checking configuration. Attached to driver: apcsmart sharenet.type = DISABLE cable.type = CUSTOM_SMART You are using a SMART cable type, so I'm entering SMART test mode mode.type = SMART Setting up serial port.

Creating serial port lock file. Hello, this is the apcupsd Cable Test program. This part of apctest is for testing Smart UPSes. Please select the function you want to perform. 1) Query the UPS for all known values 2) Perform a Battery Runtime Calibration 3) Abort Battery Calibration 4) Monitor Battery Calibration progress 5) Program EEPROM 6) Enter TTY mode communicating with UPS 7) Quit Select function number: 1 Item 1 will probe the UPS for all values known to apcupsd and present them in rather raw format. This output can be useful for providing technical support if you are having problems with your UPS. Item 2 will perform a Battery Runtime Calibration.

This test will only be performed if your battery is 100% charged. Running the test will cause the batteries to be discharged to approximately 30% of capacity. The exact number depends on the UPS model. In any case, apctest will abort the test if it detects that the battery charge is 20% or less.

The advantage of doing this test is that the UPS will be able to recalibrate the remaining runtime counter that it maintains in its firmware. As your batteries age, they tend to hold less of a charge, so the runtime calibration may not be accurate after several years. We recommend that perform a Battery Calibration about once a year. You should not perform this calibration too often since discharging the batteries tends to shorten their lifespan.

Item 3 can be used to abort a Battery Calibration in progress, if you some how became disconnected. Item 4 can be used to restart the monitoring of a Battery Calibration if you should some how become disconnected during the test. Item 5 is used to program the EEPROM. Please see the chapter of this manual for the details. Item 6 will initiate a direct communication between your terminal and the UPS, at which point you can enter raw UPS commands. Please be aware that you should be careful what commands you enter because you can cause your UPS to suddenly shutdown, or you can modify the EEPROM in a way to disable your UPS.

The details of the raw Smart mode UPS commands can be found in the chapter of this manual. Item 7 will terminate apctest.

Apcaccess is a program (normally found in /sbin/apcaccess) that permits you to print out the complete status of your UPS. Apcaccess will use the Network Information Server to obtain the necessary information.

You can specify a second optional argument to apcaccess in the form of host:port where the:port is optional. The default is localhost:3551.

Please note that in versions prior to 3.10.6, the default NIS port was 7000, so if you are mixing versions, you will need to take a lot of care to ensure that all components are using the same port. To enable the apcupsd Network Information Server, which is normally the default, you set: NETSERVER on NISPORT 3551 in your apcupsd.conf file.

The full form of the apcaccess command is: apcaccess status localhost:3551 where only apcaccess status should normally be needed. Localhost may be replaced by any machine name, fully qualified domain name, or IP address, which means that apcaccess can access any UPS on the network running the Network Information Server. The status command line option of apcaccess will produce a full printout of all the STATUS variables used by apcupsd. This can be very helpful for checking the condition of your UPS and to know whether or not apcupsd is properly connected to it. Please note that if you invoke apcaccess within the first 30 seconds of launching apcupsd, you will likely get an error message such as: APCACCESS FATAL ERROR in apcaccess.c at line 336 tcp_open: cannot connect to server localhost on port 3551. This is because apcupsd is still in the process of initializing the UPS.

The solution is to wait at least 30 seconds after starting apcupsd before launching apcaccess. When a major event is generated within apcupsd, control is passed to the script apccontrol normally found in /etc/apcupsd/apccontrol.

The event name, and a number of other important parameters are passed to the script. The major function of the apccontrol script is to perform a shutdown of the system (as well as the killpower operation). In addition, another major task for this script is to notify you by email when certain events such as powerfail occur. Since apccontrol is a script, you can customize it to your own needs using any text editor. To do so, you must have a minimal knowledge of Unix shell programming. In addition, another feature is that you can write your own scripts that will be automatically called by apccontrol before any of its own code is executed.

Details of the events and how to program them are contained in the Advanced topics section entitled. There are four CGI programs (multimon.cgi, upsstats.cgi, upsfstats.cgi, and upsimage.cgi).

To have them properly installed, you must run the './configure' command with --enable-cgi and you should specify an installation directory with --with-cgi-bin= or load them manually. The default directory for installation of the CGI programs is /etc/apcupsd, which is not really where you want them if you are going to use them. Normally, they should go in the cgi-bin of your Web server. Once built and loaded, they will give you the status of your UPS or UPSes via a web browser. Normally only multimon.cgi is directly invoked by the user.

However, it is possible to directly invoke upsstats.cgi and upsfstats.cgi. Upsimage.cgi should never be directly invoked as it is used by upsstats.cgi to produce the bar charts. Before using multimon and the other CGI programs, first ensure that apcupsd is configured to run the Network Information Server. This is done by setting NETSERVER on in /etc/apcupsd/apcupsd.conf. This switch is on by default. Next you must edit the hosts file /etc/apcupsd/hosts.conf and at the end, add the name of the hosts you want to monitor and a label string for them. For example: MONITOR matou 'Server' MONITOR polymatou 'Backup server' MONITOR deuter 'Disk server' matou, polymatou, and deuter are the network names of the three machines currently running apcupsd.

Please note that the network names may either be IP addresses or fully qualified domain names. The network name (or IP address) may optionally be followed by:port, where the port is the NIS port address you wish to use. This is useful if you are running multiple copies of apcupsd on the same system or if you are running in a mixed vendor environment where the NIS port assignments differ. An example could be the following: MONITOR matou 'Server' MONITOR polymatou 'Backup server' MONITOR deuter 'Disk server' MONITOR polymatou:7001 'APC USB UPS' where the USB copy of apcupsd has been configured to use port 7001 by modifying apcupsd.conf. Note, the default NIS port is 3551 on most platforms. To test multimon.cgi, you can execute it as non-root directly from the source cgi build directory.

To do so, enter at a shell prompt:./multimon.cgi If everything is set up correctly, it will print a bunch of HTML with the values of the machines that you have put in the hosts.conf file. It should look something like the following (note, only a small portion of the output is reproduced here): Content-type: text/html

At many sites, the Apache server is not running as root, so you must be careful to ensure that that /etc/apcupsd/hosts.conf and /etc/apcupsd/multimon.conf are world readable. To invoke multimon in your Web browser, enter: You should get something similar to the screen shot shown below. If you wish additional control over the colors, type faces, and sizes of the multimon output, you may simply edit the apcupsd.css file to specify the styles you prefer. The CGI programs compiled for Windows are included in the Windows package starting with apcupsd-3.14.7. The CGI programs included with the Windows package are intended to be run on Windows. If your web server is running on Linux or another operating system, you will need to obtain binary packages for that platform (or build them from source) instead. The windows build of the CGI programs has been tested with the Apache web server for Win32.

They should also work with MS Internet Information Server (IIS). To use the programs, copy the contents of the cgi/ directory from your apcupsd installation directory to the cgi-bin/ directory of your web server. Consult your web server's documentation for how to enable CGI programs to be executed. Sometimes special security settings are required. Configure the hosts.conf file as described above. The programs expect to find the hosts.conf file and the apcupsd.css file in the directory apcupsd etc apcupsd on the same drive letter as the web server's cgi-bin directory.

If you installed apcupsd into C: apcupsd (the default) and your web server's cgi-bin/ directory is also located on the C: drive, no further changes are necessary. If you installed apcupsd into a different directory or your web server cgi-bin is on another drive, you will need to relocate hosts.conf and apcupsd.css from the apcupsd install location to apcupsd etc apcupsd on the appropriate drive. • apcupsd runs as root. • If you have NETSERVER ON in your apcupsd.conf file (which is the default), be aware that anyone on the network can read the status of your UPS.

This may or may not pose a problem. If you don't consider this information privileged, as is the case for many, there is little risk. In addition, if you have a perimeter firewall or NATting router with typical settings only users on your local network access to your UPS information. You may also restrict access using using firewall settings (see below) or TCP Wrappers (see below). If your operating system does not support a host based firewall (a firewall running on the local machine) then you may try to get some of the functionality of such a firewall with TCP Wrappers. As of apcupsd version 3.8.2, TCP Wrappers are implemented if you turn them on when configuring./configure --with-libwrap.

With this code enabled, you may control who may access your apcupsd via TCP connections (the Network Information Server). This control is done by modifying the file: /etc/hosts.allow.

This code is implemented but untested. If you use it, please send us some feedback.

If you have a SmartUPS, there are depending on the UPS at least 12 different values stored in the EEPROM that determine how the UPS reacts to various conditions such as high line voltage, low line voltage, power down grace periods, etc. In general, for the moment, we do not recommend that you change your EEPROM values unless absolutely necessary. There have been several reported cases of problems setting the Low Transfer Voltage. Consequently, if at all possible, do not attempt to change this value.

To make the EEPROM changes with apctest you must first stop the apcupsd daemon. After apcupsd is stopped you may invoke apctest (as root).

We recommend that you change the EEPROM as little as is absolutely necessary since it is a somewhat delicate process that has occasionally produced problems (i.e. Improper EEPROM values are displayed after the update). Apctest will present a menu of options which are generally self-explanatory. Note that USB connections will show a difference set of options than smart serial connections. Sealed Lead Acid (SLA) batteries, otherwise known as Valve Regulated Lead Acid (VRLA) batteries, were originally known as 'dry batteries'. When first introduced in the 1950s, they used a gel electrolyte.

The otherwise free acid was immobilised with a fine silica powder and formed a gel substance. In the 1970s the technology moved to Absorbed Glass Mat (AGM) where the separators between the lead plates are made of highly porous micro-fine glass fibres which absorb and immobilise the acid and prevent it from spilling. A crack or hole in the casing of a VRLA battery using AGM technology will not result in a measurable electrolyte spill. Spill containment with VRLA batteries is therefore not meaningful or appropriate. AGM has became the preferred VRLA technology for use in standby or float applications and is used in UPSes in the telecommunications, power, and many other mission critical industries where the power supply must not be interrupted. APC UPSes use VRLA batteries.

VRLA batteries are designed to recombine hydrogen and oxygen and emit only extremely small amounts of hydrogen under normal operating conditions. Normal room ventilation is sufficient to remove any hydrogen, so special ventilation is not required. Most brand name UPS batteries should last 3-5 years. Some APC Back-UPS models may have a shorter battery life expectancy. Refer to the user's manual of your APC Back-UPS to determine the exact battery life expectancy or contact APC Technical Support.

Below are some APC guidelines for ensuring optimum battery life expectancy: • Make sure that you keep your APC UPS in a cool, dry location with plenty of ventilation. Ideally, the temperature where your UPS is kept should not exceed 75 Deg F (24 Deg C). Also, for ventilation purposes, leave roughly one to two inches on each side for proper airflow. • The optimum operating temperature for a lead acid battery is 25 Deg C (77 Deg F). Elevated temperature reduces longevity. As a guideline, every 8 Deg C (15 Deg F) rise in temperature will cut the battery life in half. A battery which would last for 6 years at 25 Deg C (77 Deg F), will only be good for 3 years if operated at 33 Deg C (95 Deg F).

Keep in mind that the battery temperature inside your UPS will always be warmer than the ambient temperature of the location where the UPS is installed. • Only perform runtime calibrations on your UPS one or two times a year, if necessary. Some of our customers want to check their systems to verify that their runtime is sufficient. However, consistently performing these calibrations can significantly decrease the life expectancy of your battery. • Do not store batteries for extended periods of time. New batteries can be stored for 6 to 12 months from date of purchase. After this period, the battery should be used or it will lose a great deal of its charge.

It is not advisable to store batteries that have already been in use. • Do not exceed 80 percent of a UPS unit's rated capacity due to the reduction in run time. When you increase your load, your runtime decreases. In the event of a utility power failure, a UPS loaded to full capacity will drain and discharge it's battery quickly and will decrease the life expectancy. The Smart-UPS detects line voltage distortions such as spikes, notches, dips, and swells, as well as distortions caused by operation with inexpensive fuel-powered generators.

By default, the UPS reacts to distortions by transferring to on-battery operation to protect the equipment that you are plugging into the UPS. Where power quality is poor, the UPS may frequently transfer to on-battery operation. Battery longevity and service life of the UPS may be conserved by reducing the sensitivity of the UPS, as long as your equipment can operate normally under the conditions detailed below.

Any type of voltage disturbance includes; High/Low/No RMS Voltage, Total Harmonic Distortion(THD), Change in Voltage over Time(dv/dt), Frequency (Hz) out of tolerance. High Sensitivity Mode In the event of any type of voltage disturbance, the UPS will transfer to battery power and watch the AC line until it can transfer back to line. The transfer time in this mode depends on how far the line voltage deviates from the sinewave reference. Medium Sensitivity Mode In the event of a RMS voltage-out-of-tolerance(High/Low/No) and RMS-rate-of-change disturbances(dv/dt) in the line voltage, the UPS will transfer to battery power and watch the AC line until it can transfer back to line. In this mode the transfer times are longer but still within acceptable limits to insure the continuity of a computer's operation. Low Sensitivity Mode In the event of a RMS voltage-out-of-tolerance disturbances(High/Low/No) in the line voltage, the UPS will transfer to battery power and watch the AC line until it can transfer back to line. In this mode the transfer times are longer but still within acceptable limits to insure the continuity of a computer's operation.

To change the sensitivity of the UPS, press the small, white 'sensitivity' button on the rear of the UPS. Use a pointed object (such as a pen) to do so. The default setting is 'high'; press the button once to set the sensitivity to 'medium', and press it again to set it to 'low'; pressing it a third time will set it back to 'high'. The sensitivity setting change will take effect immediately. The green LED next to the button is a sensitivity setting indicator - brightly lit is 'high' sensitivity, dimly lit is 'medium', and off is 'low' sensitivity. The battery charge graph LEDs on the front panel of a Smart-UPS will flash in unison when the UPS is operating online and the runtime remaining (calculated by the Smart-UPS microprocessor) is less than two minutes more than the low battery signal warning time (minimum of two minutes). This would usually indicate that you need to either decrease the load or install new batteries.

If the batteries are new, then you need to perform a runtime calibration (see below). At a pinch, you could also decrease the low battery warning time. There are four possible settings: 2, 5, 7, or 10 minutes. If you own your UPS for long enough, you will inevitably need to replace the UPS battery or battery cartridge. An APC battery cartridge comprises two batteries physically stuck together with double-sided tape and wired in series.

After the decision to replace the batteries, you will face another decision almost immediately: whether to purchase genuine APC replacement batteries or not. There are pros and cons to purchasing genuine replacement APC batteries. APC Battery Pros • APC batteries are supported by APC • APC batteries come with all the necessary hardware • APC batteries come as pre-made cartridges • APC batteries will physically fit your UPS APC Battery Cons • APC batteries cost up to 4 times the cost of third party batteries There are also pros and cons to purchasing third party batteries. Although you can do a hot swap of your batteries while the computer and any other connected equipment is running, it may not be very satisfactory because the UPS will not always detect that the batteries have been swapped and apcupsd will continue to report 'Low Battery'. There are several ways to correct this situation: 1.

If you have a 'smart' UPS model, you can force a self-test to make the UPS notice that the battery has been replaced. If after a self-test, the UPS does not detect that the battery has been replaced, you can use apctest to do a soft battery runtime calibration. For details of doing this, refer to the 'Soft' Runtime Calibration section below. If after the soft battery runtime recalibration, the UPS does not detect that the battery has been replaced, you will need to do a manual battery runtime calibration.

For details of doing this, refer to the 'Manual' Runtime Calibration section below. A runtime calibration causes the UPS to recalculate its available runtime capacity based on its current load. Caution: a runtime calibration will deeply discharge the UPS batteries, which can leave a UPS temporarily unable to support its equipment if a utility power failure occurs. Frequent calibrations reduce the life of batteries. APC recommends performing a runtime calibration only annually, semiannually, or whenever the load on the UPS is increased.

In order to perform a 'soft' runtime calibration it is necessary to wait for the UPS to recharge its batteries to 100% capacity. Once this has been done, you can then initiate a runtime calibration through apctest. APC Documentation Notes: 1. In order for the calibration to be accurate, the output load has to be more than 40% (some APC documentation recommends at least 30%). Also, it is advisable not to increase or reduce the load when the UPS is calibrating its run time. Under no circumstances should the UPS be turned off during a run time calibration procedure!

Once initiated, the calibration must be allowed to run until completion. The run time calibration procedure is not necessary nor advisable for a new UPS. Only old UPSes with batteries that are not subject to discharge for long periods of time should be allowed to perform a run time calibration. Matrix-UPS and Smart-UPS recalculate the runtime-related parameters every time the UPS goes on battery.

When doing a runtime calibration with 'older' batteries, APC Technical Support recommend doing a complete discharge and recharge first. If you have 'dumb' UPS (aka simple signalling) like a Back-UPS, then your only option is to do a manual runtime calibration. Most of the information in this section is taken from APC's website.

Any non-APC additions have been inserted in square brackets. For a 'smart' or 'smart signalling' Back-UPS Pro or Smart-UPS: Perform a Runtime Calibration. This is a manual procedure and should not be confused with the runtime calibration performed through PowerChute plus [or apctest]. The batteries inside of the Smart-UPS are controlled by a microprocessor within the UPS. Sometimes it is necessary to reset this microprocessor, especially after the installation of new batteries. Stop the PowerChute plus [or apcupsd] software from running and disconnect the serial cable.

There must be at least a 30% load attached to the UPS during this procedure, but the process will cause the UPS to shut off and cut power to its outlets. Therefore, attach a non-critical load to the UPS and then force the UPS on battery by disconnecting it from utility power [suggest not disconnecting, but simply turning off utility power thereby preserving earthing]. Allow the unit to run on battery until it turns off completely. Make sure a 30% load is present! Plug the UPS back into the wall outlet [switch utility power back on] and allow it to recharge (it will recharge more quickly turned off and with no load present).

Once the unit has recharged, the 'runtime remaining' calculation should be more accurate. Remember that if the unit is an older model, then the runtime will not improve significantly. Background: An APC Smart-UPS has a microprocessor which calculates runtime primarily based on the load attached to the UPS and on its battery capacity. On the right side of the front display panel there is a vertical graph of five LEDs. Each LED is an indication of battery charge in increments of twenty percent: 20, 40, 60, 80, 100% (bottom to top). For example, if the battery charge is 99%, then only four of the five LEDs are illuminated.

To ensure that an operating system receives a graceful shutdown when using PowerChute plus or a SmartSlot accessory, an alert is generated by the Smart-UPS indicating that the UPS has reached a low battery condition. The alert is audible (rapid beeping), visual (flashing battery LED or LEDs), and readable through the graphical interface of PowerChute plus software (or a native UPS shutdown program within a particular operating system.) In order to calculate this 'low battery condition,' all Smart-UPS products have a preconfigured low battery signal warning time of two minutes (this is the factory default setting). There are a total of four user-changeable settings: 2, 5, 7, or 10 minutes.

If the low battery signal warning time is set for 2 minutes, then the alerts will activate simultaneously two minutes prior to shutdown. Similarly, if the total runtime for a particular UPS is 30 minutes with a low battery signal warning time set at 10 minutes, then the UPS will run on battery for 20 minutes before the low battery alert begins. Total runtime is primarily based on two factors, battery capacity and UPS load. UPS load and runtime on battery are inversely proportional: as load increases, battery runtime decreases and vice versa. When utility power is lost, the UPS begins discharging the battery in order to support the attached load. Once power returns, the Smart-UPS will automatically begin to recharge its battery. For a Matrix UPS: It is unnecessary to subject a battery bank to an excessively long calibration.

Remove battery packs or increase the load (space heaters are good dummy loads) to obtain a reasonable time length for the calibration (under an hour if possible). At the start of a calibration, the Matrix microprocessor saves the Estimated Run Time displayed. The unit will then go to battery power until the capacity is 25%. After this run time has been completed, the original Estimated Run Time is compared with the actual run time. It will then increase or decrease this value to correspond to the new run time achieved.

If, at any time during the discharge, one of the following rules is violated the calibration will be aborted or corrupted: • Battery capacity must be 100% at start of calibration (all packs must indicated as float). • Initial 'Estimated Run Time' must not exceed 128 minutes (remove battery packs if necessary). • Load must be above 25%. • Load must not fluctuate more than ± 5%. • The UPS must be allowed to run down to 25% battery capacity.

PowerChute [or apcupsd] and Accessories must be removed since they can abort the calibration prematurely. For a 'dumb' or 'simple signalling' UPS (eg a Back-UPS): This could be done if you have changed your equipment load or battery. Stop the PowerChute [or apcupsd] software from running; disconnect the serial cable between the computer and UPS. Next unplug the UPS from the wall [suggest not disconnecting but simply turning off the utility power thereby preserving the earthing] and let it run on battery until it reaches low battery. Once it reaches low battery plug it back into the wall outlet [turn the utility power back on] and let it recharge. Recharge time can take up to 4 hours.

In some cases none of the battery runtime calibration methods result in the UPS reporting a reasonably correct battery runtime. It has been speculated that this is because the battery constant value has drifted so far from normal that the microprocessor in the UPS cannot correct it. The good news is that if you are located in the USA, all you have to do is contact APC Technical Support and they will send you a serial port dongle which plugs into the serial port of your UPS and reprograms the battery constant value for you to the correct value. The bad news is that for many users outside the USA, this service does not appear to be available.

It is, however, recommended that you first try contacting APC Technical Support to verify the correct battery constant value. The APC representatives in the Support Forum on the APC website are also very helpful in this regard. If all else fails, the information below is for you.

WARNING: Only the values for the Smart-UPS 700 model SU700 and Smart-UPS 1400 model SU1400, both with international firmware (and therefore international voltage), have been verified. YOU, gentle reader, USE THIS INFORMATION AT YOUR OWN RISK in the full knowledge that you may render your UPS inoperable and perhaps irreparable, and you will have no-one to blame but yourself.

Caveat Utilitor! See the bugs section of this document for a list of known bugs and solutions. Question: Why all the craziness with custom serial cables?

Answer: It was nothing more nor less than a form of customer control. For a long time APC wanted to keep other people from talking to its UPSes so it could lock out potential competition for its PowerChute software.

Scrambling the leads on its serial cables was a cheap way to accomplish this -- in fact, they tended to be wired so that if you tried a straight-through cable, opening a serial link to the UPS would be interpreted as a shutdown command! (Hardware companies often think like this -- they lock up interfaces by instinct, cornering a small market rather than growing a bigger one. It's fundamentally stupid and self-defeating, but it's the kind of stupid that tends to sound good at an executive meeting.) Question: What UPS brands does apcupsd support? Answer: Currently apcupsd supports only APC UPSes. However, some companies such as Hewlett Packard put their own brand name on APC manufactured UPSes. Thus even if you do not have an APC branded UPS, it may work with apcupsd.

You will need to know the corresponding APC model number. Apcupsd supports all the popular APC models. See the installation and configurations sections of this document for more details. Question: Does apcupsd support Windows?

Question: I don't have a cable, which one should I build? Answer: First you must know if you have an apcsmart UPS or a voltage-signalling UPS. If you have a apcsmart UPS, we recommend building a Custom Smart cable. (see ) If you have a voltage-signaling UPS, we recommend that you build a Custom Simple cable. (see ) Question: How much CPU resources does apcupsd use? Answer: Depending on your CPU speed, you may see more or less of the CPU consumed by apcupsd.

On a 400MHz Unix system, the CPU usage should fall well below 0.1%. On slower systems, the percentage will increase proportionally to the decrease in the CPU speed.

On a 400Mhz Win98 machine, the CPU usage will be on the order of 0.5-1.0%. This is higher than for Unix systems. However, compared to the 30% CPU usage by APC's PowerChute (the version on the CDROM shipped with my UPS), apcupsd's 0.5-1.0% is very modest. Question: What language is apcupsd written in?

Answer: It is written in C and C++. Question: To test apcupsd, I unplugged the UPS to simulate a power outage. After the machine went into the shutdown process I plugged the UPS back into the commercial power source. This caused the shutdown process to hang after the daemon tried to shut-off the ups. Have you run into this problem, and if so do you have a remedy? Answer: Normally, once the shutdown process has begun, we cannot stop it -- how do you stop a shutdown that has killed off half of the daemons running on your system? Most likely you will be left with an unusable system.

In addition, when apcupsd is re-executed in the halt script after the disks are synced, it tries to shut off the UPS power, but the UPS will generally refuse to do so if the AC power is on. Since we cannot be 100% sure whether or not the UPS will shut off the power, we don't attempt to reboot the system if we detect that the power is back as it might then get caught by a delayed power off (at least for Smart UPSes). Question: After running apcupsd for a while, I get the following error: 'Serial communications with UPS lost.'

What is the problem? Answer: We use standard Unix serial port read() and write() calls so once a connection is made, we generally have few problems. However, there have been reports that APC's SNMP Management Card can cause serial port problems. If you have such a card, we suggest that you remove it and see if the problem goes away.

It is also possible that some other process such as a getty is reading the serial port. Question: I get the following error: Starting apcupsd power management.

Mar 20 21:19:40 box apcupsd[297]: apcupsd FATAL ERROR in apcserial.c at line 83. Cannot open UPS tty /dev/cua01: No such file or directory. What is the problem?

Answer: The two most likely causes of your problem are: 1. You have the wrong serial port device name in the apcupsd.conf file. The device name is not defined on your system.

Suggestions for proceeding:For the first item, check what your serial port device should be named. You might be able to find the name with an: ls /dev Normally there will be hundreds or even thousands of names that print. If that doesn't produce anything useful, you can try step 2. Perhaps your device is not defined. To get more information on your devices try ' man MAKEDEV' or ' find / -name MAKEDEV'. It is often located in /dev/MAKEDEV. Looking at the documentation may tell you what the correct name is, or at least allow you to create the device.

Question: How do I ensure that the slaves shutdown before the master? Answer: Slaves make their shutdown decision independently from the master. Therefore you can use the TIMEOUT, MINUTES, and BATTERYLEVEL settings in the slaves' apcupsd.conf to configure them to shut down before the master. Question: How do I ensure that my database server is correctly shutdown? Answer: You simply add whatever commands are necessary in the appropriate case statements in /etc/apcupsd/apccontrol, which is a standard script file that is called to actually do the shutdown. Alternatively, you can add your own script file that will be called before doing the commands in apccontrol. Your script file must have the same name as the appropriate case statement in apccontrol; it must be executable; and it must be in the same directory as apccontrol.

When apcupsd detects anomalies from your UPS device, it will make some decisions that usually result in one or more calls to the script located in /etc/apcupsd/apccontrol. The apccontrol file is a shell script that acts on the first argument that apcupsd passes to it. These actions are set up by default to sane behavior for all situations apcupsd is likely to detect from the UPS.

However, you can change the apccontrol behavior for every single action. To customize, so create a file with the same name as the action, which is passed as a command line argument.

Put your script in the /etc/apcupsd directory. These events are sent to the system log, optionally sent to the temporary events file ( /etc/apcupsd/apcupsd.events), and they also generate a call to /etc/apcupsd/apccontrol which in turn will call any scripts you have placed in the /etc/apcupsd directory. Normally, /etc/apcupsd/apccontrol is called only by apcupsd.

Consequently, you should not invoke it directly. However, it is important to understand how it functions, and in some cases, you may want to change the messages that it prints using wall. We recommend that you do so by writing your own script to be invoked by apccontrol rather than by modifying apccontrol directly. This makes it easier for you to upgrade to the next version of apcupsd In other case, you may want to write your own shell scripts that will be invoked by apccontrol.

For example, when a power fail occurs, you may want to send an email message to root. To write your own routine for the powerout action, you create shell script named powerout and put it in the lib directory (normally /etc/apcupsd). When the powerout action is invoked by apcupsd, apccontrol will first give control to your script. If you want apccontrol to continue with the default action, simply exit your script with an exit status of zero. If you do not want apccontrol to continue with the default action, your script should exit with the special exit code of 99. However, in this case, please be aware that you must ensure proper shutdown of your machine if necessary.

Some sample scripts (onbattery and mainsback) that email power failure messages can be found in /etc/apcupsd after an install or in the platforms/etc directory of the source code. When apcupsd detects an event, it calls the apccontrol script with four arguments as: apccontrol event ups-name connected powered where: event is the event that occurred and it may be any one of the values described in the next section.

Ups-name is the name of the UPS as specified in the configuration file (not the name in the EEPROM). Connected is 1 if apcupsd is connected to the UPS via a serial port (or a USB port). In most configurations, this will be the case. In the case of a Slave machine where apcupsd is not directly connected to the UPS, this value will be 0.

Powered is 1 if the computer on which apcupsd is running is powered by the UPS and 0 if not. At the moment, this value is unimplemented and always 0.

The following event names are supported: annoyme When a shutdown is scheduled, and the time specified on the ANNOYME directive in the apcupsd.conf file expires, this event is generated. Default: wall a message changeme When apcupsd detects that the mains are on, but the battery is not functioning correctly, this event is generated.

It is repeated every x hours. Default: wall a message commfailure This event is generated each time the communications line with the computer is severed. This event is not detected on dumb signaling UPSes. Default: wall a message commok After a commfailure event is issued, when the communications to the computer is re-established, this event will be generated. Default: wall a message doreboot This event is depreciated and should not be used.

Default: Shuts down the system using shutdown -h or similar doshutdown When the UPS is running on batteries and one of the limits expires (time, run, load), this event is generated to cause the machine to shutdown. Default: Shuts down the system using shutdown -h or similar emergency Called for an emergency system shutdown. (What triggers such a shutdown is unclear.) After completing this event, apcupsd will immediately initiate a doshutdown event.

Default: wall a message failing This event is generated when the UPS is running on batteries and the battery power is exhausted. The event following this one will be a shutdown.

Default: wall a message loadlimit This event is generated when the battery charge is below the low limit specified in the apcupsd.conf file. After completing this event, apcupsd will immediately initiate a doshutdown event.

Default: wall a message powerout This event is generated immediately when apcupsd detects that the UPS has switched to batteries. It may be due to a short powerfailure, an automatic selftest of the UPS, or a longer powerfailure. Default: wall a message onbattery This event is generated 5 or 6 seconds after an initial powerfailure is detected.

It means that apcupsd definitely considers the UPS to be on batteries. The onset of this event can be delayed by the ONBATTERYDELAY apcupsd.conf configuration directive. Default: wall a message offbattery This event is generated when the mains return only if the onbattery event has been generated.

Default: wall a message mainsback This event is generated when the mains power returns after a powerout condition. The shutdown event may or may not have been generated depending on the parameters you have defined and the length of the power outage. Default: nothing remotedown This event is generated on a slave machine when it detects either that the master has shutdown, or that a onbattery situation exists and the communications line has been severed. Default: wall a message runlimit This event is generated when the MINUTES value defined in the apcupsd.conf file expires while in a power fail condition. The MINUTES is the remaining runtime as internally calculated by the UPS and monitored by apcupsd. After completing this event, apcupsd will immediately initiate a doshutdown event.

Default: wall a message timeout This event is generated when the TIMEOUT value defined in the apcupsd.conf file expires while in a power fail condition. It indicates that the total time in a power failure has been exceeded and the machine should be shutdown. After completing this event, apcupsd will immediately initiate a doshutdown event. Default: wall a message startselftest This event is generated when apcupsd detects a self test by the UPS.

Normally due to the 6 second onbattery delay default time, self test events are not detected. Default: nothing endselftest This event is generated when the end of a self test is detected. Default: nothing battdetach This event is generated when apcupsd detects that the UPS battery has been disconnected. Default: nothing battattach This event is generated when apcupsd detects that the UPS battery has been reconnected after a battdetach event. Default: nothing.

The following discussion does not apply to Windows servers. Apcupsd on Windows is limited to a single instance and cannot support monitoring multiple UPSes. If you have multiple UPSes in use, you may wish to consolidate the monitoring of all of these UPSes onto a single machine, which we shall call the 'UPS server'. Generally one of the UPSes is powering the 'UPS server' itself (and possibly other machines as well).

The remaining UPSes are powering additional machines. Apcupsd can work quite well in this environment by running one instance of apcupsd on the UPS server for each UPS to be controlled.

That is, you install a single copy of apcupsd but launch it multiple times using different configuration files and scripts. (Older versions of apcupsd required you to actually compile the daemon multiple times with different configure options. This is no longer required, as all necessary adjustments can be made in apcupsd.conf.) Additionally, you will run one instance of apcupsd on each of the machines you wish to be shut down. You will configure each of these apcupsd's to use the 'net' driver to read UPS status from the proper instance of apcupsd on the UPS server. See for more information on the 'net' driver and setting up net clients. The following instructions come from the APC knowledge base: The Network Management Card (AP9617, AP9618, AP9619) must be configured with network settings before it can communicate on the network.

Once the cards have been configured with an IP address, Subnet Mask, and Default Gateway the cards can be access, managed, and controlled from other computers on the network. There are two ways to configure the Network Management Card (NMC) with its initial settings: the (windows) Wizard and Address Resolution Protocol (ARP).

The wizard in included on the CD that comes with the card. The wizard must run on a Windows operating system. You can configure the card using the wizard over the network via FTP.

If using the wizard please note, the un-configured NMC must be on the same subnet as the computer running the wizard. Address resolution protocol (arp) can also be used to configure the NMC. The MAC Address of the NMC is needed for this method of configuration. The MAC address is located on the quality assurance slip that is shipped with the NMC, and is also located on the white sticker on the NMC itself. From a computer on the same subnet as the un-configured NMC, follow the instructions: Open up a command prompt and type the following (replacing and with the actual values): arp -s Next, use Ping with a size of 113 bytes to assign the IP address defined by the ARP command. - Linux command format: ping -s 113 - Windows command format: ping -l 113. After the SNMP Network Management Card is configured with an IP address, the SNMP Card is ready for general configuration.

This is accomplished by telneting to the SNMP Card. There are two shutdown parameters that must be set in the SNMP card to ensure that connected servers shutdown quietly. These parameters can be set via the telnet terminal or the web browser interface.

• Shutdown Delay (sec) • Return Battery Capacity (%) One of the draw-backs of SNMP communication to the UPS is that the Stand-alone or Primary server must issue the power down command to the UPS early in server halt procedure. This server must issue an early command to the SNMP UPS to power down before its ethernet service is halted.

This creates a potential problem where the UPS may kill power to any connected servers before these affected servers' halt scripts complete a successful shutdown. The SNMP Shutdown Delay parameter is used to delay the UPS from killing power to its load by a prescribed period of seconds. The delay should be long enough to ensure that the Stand-alone or Primary server has enough time to successfully halt. The prescribed time should at least be 180 seconds. Any additional computers connected to the SNMP UPS must not be configured to issue the command to initiate UPS power down. These servers can be thought of as secondary stand-alone server. The APCUPSD daemons of secondary servers should be configured to initiate server halt a prescribed period of time before the Primary server issues the UPS power down command.

The Return on Battery Capacity is useful during intermittent sequential power failures. This parameter insures that the UPS will not restore power to its loads until it has recharged it battery to a prescribed percentage.

This parameter should be set to a value greater than value that the APCUPSD daemons configured 'BATTERYLEVEL' shutdown of any connected servers. This will ensure that when the UPS restores power, any additional power failures will successfully re-trigger a server shutdown. (Requires apcupsd-3.12.0 and later) By default, APCUPSD will poll the SNMP UPS card once per minute. In this case, server notification of UPS alarms could potentially be delayed one minute. Event trap catching mitigates this shortcoming. Any UPS alarms are instantly sent to prescribe servers connected SNMP UPS. These servers are referred to as Event Trap Receivers.

The SNMP UPS card can be configure to send event traps to a maximum of four receivers that will 'catch' these events. Event trap receivers IP address can be set using a telnet terminal or web browser interface. Also, be aware that servers configured to be Event Trap Receivers should have static IP set. Severs obtaining IPs from DHCP server will not catch instantaneous Events if the IP address changes from the address set in the SNMP UPS. The previous sections describe configuration of the actual SNMP card.

The remaining sections describe configuration of the APCUPSD to communicate using SNMP Protocol. To enable the SNMP support it is enough to configure the correct device in your apcupsd.conf configuration file. The directive needed for this configuration is: DEVICE::.where the directive is made by four parts. All but the first may be omitted completely or left empty to accept the default.

• host: IP address or DNS hostname of the UPS (required) • port: Remote SNMP port (optional, default: 161) • vendor: The type of SNMP MIB available on the UPS (optional, default: autodetect). Allowable choices for vendor are: • APC: APC PowerNet MIB, used on most APC brand UPSes • RFC: RFC1628 MIB, used by some non-APC UPSes • MGE: MGE MIB, used by many MGE brand UPSes • blank: Autodetect Append '_NOTRAP' to the vendor name to disable SNMP trap catching (ex: 'APC_NOTRAP'). • community: The read-write community string, usually 'private'. You can specify a read-only community string, usually 'public', if you do not require killpower support. If the community string is omitted, apcupsd will attempt to autotedect by trying 'private' and 'public'.

(optional, default: autodetect). A NIS Server/Client (Master/Slave) configuration with multiple servers is still applicable. However, an alternative configuration is possible with an SNMP enabled UPS. In this arrangement, all connected servers will be configured as a standalone server.

Each will independently communicate to the UPS. One (primary) server will be chosen to manage the task of commanding the UPS to power down.

All remaining (secondary) servers will be configured to quietly power down before the primary server issues the UPS power down command. Apcupsd-3.11.14 introduces support for SNMP trap catching. Previous versions polled the UPS status once per minute, leading to significant delays before UPS state changes were recognized.

With SNMP trap handling, apcupsd monitors the SNMP trap port and will re-poll the UPS whenever a trap is received. This happens, for example, when the UPS switches on or off battery. In order for this feature to work, you must configure your UPS to deliver traps to the server running apcupsd. This is generally done by connecting to your SNMP card via a web browser or telnet connection. You will need to enter your server's IP address as a trap receiver and make sure trap delivery is enabled.

Trap catching can lead to problems if you are already running another SNMP trap daemon on your server. Only one daemon can listen to the trap port, so whichever one is started first will succeed and the others will fail. Apcupsd will fall back to polling behavior if it is unable to open the trap port. You can also forcibly disable trap catching by appending _NOTRAP to your vendor string in the apcupsd.conf DEVICE directive. Currently (as of 3.10.0) the code to power off the UPS needs special configuration.

The killpower command for SNMP UPSes can not be issued during shutdown as typically at some time during shutdown operations the network stack is stopped. To overcome this problem it is needed to modify the /etc/rc.d/apcupsd system control script to tell apcupsd to issue the power down command (killpower) to the UPS immediately before apcupsd initiates the system shutdown.

For this reason it is paramount to set your UPS grace time to a value greater than 120 seconds to allow for clean shutdown operations before the UPS removes the power from its plugs. To enable correct shutdown operation during powerdown do the following: • Connect to your Web/SNMP card using your favorite web browser, go to the UPS configuration menu and change the 'Shutdown Delay' parameter to 180 seconds or more, depending on how much time your system shutdown requires to umount all the filesystems. • Option 1 (non-windows) Edit the server halt script. Relocate the ups_kill_power() function higher in the shutdown sequence, primarily before the command to bring down the ethernet service.

This is the preferred method for shutting down the UPS. The UPS will power down after the prescribed 'Shut Down Delay' time (in seconds) has elapsed.

• Option 2 Change /etc/rc.d/apcupsd script adding the --kill-on-powerfail to the apcupsd invocation. This method is not preferred because the UPS is commanded to power down without delay. This creates the potential for UPS powering down before the server calling for UPS power down completes its shutdown. However, in the case of Microsoft Windows OS, this is the only method available for powering down the UPS. • Restart your apcupsd With this setup your UPS operations should be safe. This feature is somewhat outdated and not often used.

Data logging consists of periodically logging important data concerning the operation of the UPS. For the definitive definition of the format, see log_data() in apcreports.c.

The format varies according to the UPS model and the information available from the UPS. For UPS models, NBKPRO, SMART, SHARESMART, and MATRIX, the output is written in a format very similar to what PowerChute writes. That is: MinLineVoltage, MaxLineVoltage, OutputVoltage, BatteryVoltage, LineFrequency, LoadPercent, UPSTemperature, AmbientTemperature, Humidity, LineVoltage, BatteryCharge, toggle Any value that is not supported by your UPS such as AmbientTemperature and Humidity will be blank or possibly as 0.0. In any case the commas before and after that field will still be output. The toggle value alternates from 0 to 1 on each line.

This was added at user request so that no two adjacent samples are identical. An actual example from the log file is: Nov 2 12:43:05 matou apcupsd[23439]: 224.9,227.5,226.2,27.74,50.00,100.0,30.6,,,226.2,50.0,1. In order to ensure that the data logged to syslog() can be directed to different files, I have assigned syslog() levels to each of our four types of data as follows: • DEBUG logging has level LOG_DEBUG • DATA logging has level LOG_INFO • STATUS logging has level LOG_NOTICE • EVENTS logging has levels LOG_WARNING, LOG_ERR, LOG_CRIT, and LOG_ALERT It should be noted that more work needs to be done on the precise definitions of each of the levels for EVENTS logging. Currently, it is roughly broken down as follows: LOG_WARNING general information such as startup, etc. LOG_ERR an error condition detected, e.g. Communications problem with the UPS. LOG_CRIT a serious problem has occurred such as power failure, running on UPS batteries.

LOG_ALERT a condition that needs immediate attention such as pending system shutdown. The default Facility for syslog() logging is DAEMON, although this can be changed with the FACILITY directive in apcupsd.conf. In the following example, we should the facility as local0. More work needs to be done to the code to ensure that it corresponds to the above levels. The Windows version of apcupsd has been tested on Win95, Win98, WinMe, WinNT, WinXP, and Win2000 systems.

This version of apcupsd has been built to run natively on Windows (no Cygwin or other emulation layer needed). Even though the Win32 version of apcupsd is a port that relies on many Unix features, it is just the same a true Windows program.

When running, it is perfectly integrated with Windows and displays its icon in the system icon tray, and provides a system tray menu to obtain additional information on how apcupsd is running (status and events dialog boxes). Once installed apcupsd normally runs as a system service. This means that it is immediately started by the operating system when the system is booted, and runs in the background even if there is no user logged into the system.

If you are installing Apcupsd for the first time, the installer will give you an opportunity to edit the apcupsd.conf configuration file to contain the values appropriate for your site. (Subsequent installations will maintain your existing apcupsd.conf, so you need not edit it again unless there are new features or syntax changes that must be accounted for.) The default configuration calls for a USB connected UPS. This is the most common connection for modern UPSes, especially those used with Windows computers. All other apcupsd drivers are available (apcsmart, dumb, net, snmp, pcnet) and can be used simply by editing the configuration file UPSCABLE, UPSTYPE, and DEVICE settings as described elsewhere in this manual. Note that on Windows, serial ports are specified using COM1, COM2, etc. Notation instead of the UNIX-style /dev/tty* notation.

Free Download Driver Modem Bolt E5372s here. Note also if you are using WinNT or Win2000, the operating system may probe the serial port attempting to attach a serial mouse. This will cause apcupsd to be unable to communicate with the serial port.

If this happens, or out of precaution, you can edit the c: boot.ini file. Find the line that looks something like the following: multi(0)disk(0)rdisk(0)partition(1) WINNT='Windows NT Workstation Version 4.00' and add the following to the end of the line: /NoSerialMice:COM1 (or COM2 depending on what you want to use). The new line should look similar to. Multi(0)disk(0)rdisk(0)partition(1) WINNT='Windows NT Workstation Version 4.00' /NoSerialMice:COM1.where the only thing you have changed is to append to the end of the line. This addition will prevent the operating system from interfering with apcupsd.

The installer will give you an opportunity start the Apcupsd service immediately. If you choose to start it manually, you may do so by selecting the 'Start Apcupsd' link from the Start->Programs->Apcupsd folder. On Windows NT/2000/XP, you may alternatively go to the Control Panel, open the Services folder, select Apcupsd UPS Server, and then click on the Start button as shown below: If the Services dialog reports a problem, it is normally because your DEVICE statement does not contain the correct serial port name. You probably should also click on the Startup. Button to ensure that the correct defaults are set. The dialogue box that appears should have Startup Type set to Automatic* and **Logon should be set to System Account.

If these values are not set correctly by default, please change them otherwise apcupsd will not work. For WinXP and Win2K systems, the dialogs are a bit different from those shown here for WinNT, but he concept is the same. You get to the Services dialog by clicking on: Control Panel ->Administrative Tools ->Component Services. The apcupsd service should appear in the right hand window when you click on Services (Local) in the left hand menu window. That should complete the installation process.

When the system tray icon turns from a question mark into a plug, right click on it and a menu will appear. Select the Events item, and the Events dialogue box should appear. There should be no error messages. By right clicking again on the system tray plug and selecting the Status item, you can verify that all the values for your UPS are correct. When the UPS switches to the battery, the battery icon will appear in the system tray. While the UPS is online, if the battery is not at least 99% charged, the plug icon will become a plug with a lightning bolt in the middle to indicate that the battery is charging.

Starting with version 3.14.2, the tray icon is provided by a separate program called 'apctray'. This cleanly separates the user interface from the daemon (service) and is required for tray icon support on Windows Vista. Note that if you close or disable the tray icon this does not stop or disable the apcupsd service which will continue to monitor the UPS and shutdown the computer when appropriate. To stop or disable the service, use the service control panel. Apctray has the capability of monitoring multiple apcupsd instances using apcupsd's Network Information Server (NIS). It will create a new icon for each instance being monitored.

By default, apctray monitors the local apcupsd (localhost on port 3551). To add additional monitors, you can right-click an existing icon and choose 'Add Monitor'.

To remove a monitor, right-click its icon and choose 'Remove Monitor'. To change thr settings for an existing monitor (ip address, port, refresh rate), right-click its icon and choose 'Configure.'

Apctray can be installed standalone (without apcupsd) if you wish to use it only to monitor remote apcupsd instances. This can be convenient for keeping an eye on a room full of UPSes from your desktop. Download and run the normal apcupsd installer and simply uncheck all components except apctray. Then add as many monitors as you wish as described above. It would be hard to overemphasize the need to do a full testing of your installation of apcupsd as there are a number of reasons why it may not behave properly in a real power failure situation. Please read the section of this document for general instructions on testing the Win32 version. However, on Win32 systems, there is no Unix system log file, so if something goes wrong, look in the file c: apcupsd etc apcupsd apcupsd.events where apcupsd normally logs its events, and you will generally find more detailed information on why the program is not working.

The most common cause of problems is either improper configuration of the cable type, or an incorrect address for the serial port. Additionally, check the application event log, if you're running a platform that supports it such as Windows 2000 or XP. An upgrade may be accomplished by uninstalling the old version (using the Add/Remove Programs Control Panel or clicking the 'Uninstall Apcupsd' link from Start ->Programs ->Apcupsd. Near the end of the uninstall you will be prompted about removing configuration and event files.

You should answer 'No' in order to preserve your existing apcupsd.conf file. After the uninstall completes you may install the new version of Apcupsd as described above. If you preserved your existing apcupsd.conf file, the new apcupsd.conf will be installed as apcupsd.conf.new.

On some Windows systems, the domain resolution does not seem to work if you have not configured a DNS server in the Network section of the Control Panel. This problem should be apparent only when running a slave configuration. In this case, when you specify the name of the master in your apcupsd.conf file, apcupsd will be unable to resolve the name to a valid IP address. To circumvent this problem, simply enter the address as an IP address rather than a hostname, or alternatively, ensure that you have a valid DNS server configured on your system. On WinNT, WinXP, and Win2K systems, you can examine the System Applications log to which apcupsd writes Windows error messages during startup.

Regardless of which Windows system you are running, apcupsd logs most error messages to c: apcupsd etc apcupsd apcupsd.events. This type error messages such as configuration file not found, etc are written to this file.

Note that on some systems (WinXP, possibly others) Apcupsd is unable to write to this file when running as a service. It is possible to receive email notification of apcupsd events using some simple Visual Basic scripts contributed by Ed Dondlinger. The scripts are automatically installed in the etc/apcupsd directory of your apcupsd installation but are disabled by default.

To enable them, first open them in a text editor such as Notepad and edit the USER VARIABLES section to set your email preferences including address, server information, etc. Then rename the script files without the *.example suffix. Scripts are supplied for onbattery, offbattery, and commfailure events.

You can copy the scripts to other filenames and modify the email body text to respond to other events as described in. If your batteries become exhausted during a power failure and you want your machine to automatically reboot when the power comes back, it is useful to implement the killpower feature of the UPS where apcupsd sends the UPS the command to shut off the power. In doing so, the power will be cut to your PC and if your BIOS is properly setup, the machine will automatically reboot when the power comes back. This is important for servers. This feature is implemented on Unix systems by first requesting a system shutdown.

As a part of the shutdown, apcupsd is terminated by the system, but the shutdown process executes a script where apcupsd is recalled after the disks are synced and the machine is idle. Apcupsd then requests the UPS to shut off the power (killpower).

Unfortunately on Windows, there is no such shutdown script that we are aware of and no way for apcupsd to get control after the machine is idled. If this feature is important to you, it is possible to do it by telling apcupsd to immediately issue the killpower command after issuing the shutdown request. The danger in doing so is that if the machine is not sufficiently idled when the killpower takes place, the disks will need to be rescanned (and there is a possibility of lost data however small). Generally, UPSes have a shutdown grace period which gives sufficient time for the OS to shutdown before the power is cut. To implement this feature, you need to add the -p option to the apcupsd command line that is executed by the system. Currently the procedure is manual.

You do so by editing the registry and changing the line: c: apcupsd apcupsd.exe /service found under the key: HKEY_LOCAL_MACHINE Software Microsoft Windows CurrentVersion RunServices to c: apcupsd apcupsd.exe /service -p If you have a Smart UPS, you can configure the kill power grace period, and you might want to set it to 3 minutes. If you have a dumb UPS, there is no grace period and you should not use this procedure. If you have a Back-UPS CS or ES, these UPSes generally have a fixed grace period of 2 minutes, which is probably sufficient. Our philosophy is to shutdown a computer but not to power it down itself (as opposed to having the UPS cut the power as described above). That is we prefer to idle a computer but leave it running. This has the advantage that in a power fail situation, if the killpower function described above does not work, the computer will continue to draw down the batteries and the UPS will hopefully shutoff before the power is restore thus permitting an automatic reboot.

Nevertheless some people prefer to do a full power down. To do so, you might want to get a copy of PsShutdown, which does have a power down option. You can find it and a lot more useful software at:. To use their shutdown program rather than the apcupsd supplied version, you simply edit: c: apcupsd etc apcupsd apccontrol with any text editor and change our calls to shutdown to psshutdown. These options are not normally seen or used by the user, and are documented here only for information purposes. At the current time, to change the default options, you must either manually run apcupsd or you must manually edit the system registry and modify the appropriate entries. In order to avoid option clashes between the options necessary for apcupsd to run on Windows and the standard apcupsd options, all Windows specific options are signaled with a forward slash character ( /), while as usual, the standard apcupsd options are signaled with a minus ( -), or a minus minus ( --).

All the standard apcupsd options can be used on the Windows version. If you have a UPS that communicates via serial port, you need to do two things before you can even think about configuring the software. First, you need to figure out whether it's a dumb (voltage-signalling) UPS or speaks the apcsmart protocol. Second, if you have an interface cable from APC, you need to figure out what kind it is. If you don't have such a cable, you need to build one. A straight-through serial cable won't work. According to Bill Marr the Belkin F5U109, also sold as F5U409 also works with apcupsd for kernel versions 2.4.25 or higher and kernels 2.6.1 and higher.

These newer kernels are needed to have the patch that makes the mct_u232 (Magic Control Technology) module and other adapters work with RS-232 devices that do not assert the CTS signal. By using a special adaptor, you can connect your serial-line UPS to a USB port. If you would like to free up your serial port and connect your existing serial port UPS to a USB port, it is possible if you have one of the later kernels. You simply get a serial to USB adapter that is supported by the kernel, plug it in and make one minor change to your apcupsd.conf file and away you go. (Kern adds: Thanks to Joe Acosta for pointing this out to me.) The device that Joe Acosta and Kern are using is IOgear GUC232A USB 2 serial adapter.

Bill Marr informs us that it also works with a Back-UPS Pro 650 and the 940-0095B cable. At Kern's site, running Red Hat 7.1 with kernel 2.4.9-12, he simply changed his /etc/apcupsd/apcupsd.conf configuration line to be: DEVICE /dev/ttyUSB0 Depending on whether or not you have hotplug working, you may need to explicitly load the kernel modules usbserial and pl2303. In Kern's case, this was not necessary.

If you have a serial-line UPS, there are some tests you should run before the general ones described in the section. To test your computer's connection with a serial-line UPS, you first need to establish that the serial line is functioning, and then that the UPS is responding to commands. This can be a bit tricky, especially with a dumb voltage-signalling interface, because it is completely quiescent when there are no commands being passed, and the command repertoire doesn't include any self-tests. Because it is easy to configure a serial cable incorrectly in such a way as to cause premature shutdowns of the UPS power, we strongly recommend, especially for voltage- signaling (dumb) UPSes, that you do most of the initial testing with your computer plugged into the wall rather than your UPS.

Thus if the UPS power is suddenly shut off, your computer will continue to run. We also recommend using safe-apccontrol as described below, until you are sure that the signaling is correct.

Also note that if you launch the execution of apcupsd while your voltage-signaling UPS is on battery power, it is very likely that your UPS will immediately shut off the power. This is due to the initialization of the serial port line signals, which often looks to the UPS like a shutdown command. Finally, double-check the state of your cabling and UPS indicator lights frequently during testing. For voltage-signaling UPSes, apcupsd is not currently able to detect whether or not the serial cable is connected.

In addition, some simple signaling UPSes with certain cable combinations are not able to detect the low battery condition. For more details please see. Once you have compiled, installed, and invoked apcupsd, you should wait to allow apcupsd to configure itself and establish contact with the UPS.

If you see a message similar to the following about 30 seconds after starting apcupsd. Apcupsd FATAL ERROR in apcserial.c at line 156 PANIC! Cannot communicate with UPS via serial port. It means that apcupsd tried for about 30 seconds to establish contact with the UPS via the serial port, but was unable to do so. Before continuing, you must correct this problem.

Some of the possible sources of the problem are: • You have not configured the correct serial port name on the DEVICE directive in your apcupsd configuration file. • The serial port that you have chosen has logins enabled. You must disable logins on that port, otherwise, the system prevents apcupsd from using it. Normally, the file /etc/inittab specifies the ports for which a getty process is started (on Sun machines, the serial port program equivalent to getty is called ttymon). You must disable this for the port that you wish to use.

• Make sure you are doing your testing as root otherwise, you may have permissions problems accessing the serial port. • You may have cabling problems, either with an incorrect cable, or the incorrect cable specification directive in the configuration file. • You may have a problem with the /etc/apcupsd/acpupsd.conf file.

For example, check that you have specified the correct type of UPS and the correct networking directives. For more details, see the section. • If you have a SmartUPS 5000 RM 15U or similar model, that comes with a 'Web/SNMP management card' in one of the 'Smart Slots', this card may interfere with the serial port operation. If you are having problems, please remove this card and try again.

Supposedly V3.0 of the card firmware has been corrected to properly release the serial port. • Ensure that you have no other programs that are using the serial port. One user reported that he had problems because the serial port mouse (gpm) was using the same port as apcupsd.

This causes intermittent seemingly random problems. • Try connecting your UPS to another machine. If it works, then you probably have a bad serial port card. As unlikely as this may sound, at least two of our users have had to replace bad serial port cards. • Try doing an ' lsof /dev/ttyS0' where you replace the /dev/ttyS0 with your serial port name. If you get no output, the port is free (or there is no physical port).

If you get output, then another program is using the port, and you should see which one. • Try doing a ' dmesg grep tty'. This may show you if a program has grabbed the port.

(Thanks to Joe Acosta for the suggestion.) • If all else fails, make sure your system is configured for serial port support. The first thing to do is to look at your log file, usually /var/log/messages because apcupsd writes more detailed information to the log file whenever there is an error. If you have a UPS that uses apcsmart protocol, you can manually test the serial communications with the UPS by starting a serial port communications program (such as minicom, tip, or cu) with the settings 2400 8N1 (2400 baud, 8 data bits, no parity, 1 stop bit). Be extremely careful what you send to your UPS as certain characters may cause it to power down or may even cause damage to the UPS. Try sending an upper case Y to the UPS (without a return at the end). It should respond with SM. If this is not the case, review the possible problems listed above.

If you fat finger the Y and enter y instead, no cause for alarm, you will simply get the APC copyright notice. Once you are sure that serial port communications is working, proceed to the next test. The most frequently encountered problem with voltage-signalling UPSes (e.g.

BackUPS 650) is that you have incorrectly specified which cable is being used. All cables furnished by APC have the cable number stamped on the side of the computer connector end of the cable. Using this number with apcupsd will normally work fine. If you do not know what cable you have, you can use the apctest program to determine the type of the cable. For simple signaling UPSes, you should not use simple in the cable specification (i.e. UPSCABLE simple) unless you have made the cable yourself according to the wiring diagram given in the cables chapter of this manual.

You can either use the cable that came with your UPS (the easiest if we support it) or you can make your own cable. We recommend that you obtain a supported cable directly from APC. If you already have an APC cable, you can determine what kind it is by examining the flat sides of the two connectors where you will find the cable number embossed into the plastic. It is generally on one side of the male connector. To make your own cable you must first know whether you have a UPS that speaks the apcsmart protocol or a 'dumb' UPS that uses serial port line voltage signalling. If you have an smart UPS, and you build your own cable, build a Smart-Custom cable (see ).

If you have a voltage-signalling or dumb UPS, build a Simple-Custom cable (see ). If you have a BackUPS CS with a RJ45 connector, you can build your own Custom-RJ45 cable (see ). You do not have this cable unless you built it yourself. The Smart-Custom cable is not an APC product. SMART-CUSTOM CABLE Signal Computer UPS DB9F DB9M RxD 2 -------------------- 2 TxD Send TxD 3 -------------------- 1 RxD Receive GND 5 -------------------- 9 Ground When using this cable with apcupsd specify the following in apcupsd.conf: UPSCABLE smart UPSTYPE apcsmart DEVICE /dev/ttyS0 (or whatever your serial port is) If you have an OS that requires DCD or RTS to be set before you can receive input, you might try building the standard APC Smart 940-0024C cable listed below (see ). You do not have this cable unless you built it yourself.

The Simple-Custom cable is not an APC product. If you have a BackUPS CS, you are probably either using it with the USB cable that is supplied or with the 940-0128A supplied by APC, which permits running the UPS in dumb mode. By building your own cable, you can now run the BackUPS CS models (and perhaps also the ES models) using smart signalling and have all the same information that is available as running it in USB mode. The jack in the UPS is actually a 10 pin RJ45. However, you can just as easily use a 8 pin RJ45 connector, which is more standard (ethernet TX, and ISDN connector).

It is easy to construct the cable by cutting off one end of a standard RJ45-8 ethernet cable and wiring the other end (three wires) into a standard DB9F female serial port connector. Apparently, all APC voltage-signalling UPSes with DB9 serial ports have the same signals on the output pins of the UPS. The difference at the computer end is due to different cable configurations. Thus, by measuring the connectivity of a cable, one can determine how to program the UPS. The signals presented or accepted by the UPS on its DB9 connector using the numbering scheme listed above is: UPS Pin Signal meaning 1 On battery power (this signal is normally low but goes high when the UPS switches to batteries). 3 ->Mains down (line fail) See Note 1 below. 5 ->Low battery.

See Note 1 below. 6 ->Inverse of mains down signal. See Note 2 below.

Supported Models: Simple Signaling such as BackUPS Contributed by: Lazar M. Fleysher Although we do not know what the black box semiconductor contains, we believe that we understand its operation (many thanks to Lazar M. Fleysher for working this out). This cable can only be used on voltage-signalling UPSes, and provides the On Battery signal as well as kill UPS power. Most recent evidence (Lazar's analysis) indicates that this cable under the right conditions may provide the Low Battery signal. This is yet to be confirmed.

This diagram is for informational purposes and may not be complete. We don't recommend that use it to build you build one yourself. APC Part# - 940-0020B Signal Computer UPS DB9F DB9M CTS 8 -------------------- 2 On Battery DTR 4 -------------------- 1 Kill power GND 5 ---------------*---- 4 Ground --- *---- 9 Common DCD 1 ---- /// ----------- 5 Low Battery RTS 7 ---- /// (probably a --- semi-conductor).

Supported Models: Simple Signaling such as BackUPS This cable can only be used on voltage-signalling UPSes, and provides the On Battery signal, the Low Battery signal as well as kill UPS power. You may specify UPSCABLE 940-0020C. This diagram is for informational purposes and may not be complete. We don't recommend that use it to build you build one yourself. APC Part# - 940-0020C Signal Computer UPS DB9F DB9M CTS 8 -------------------- 2 On Battery DTR 4 -------------------- 1 Kill power GND 5 ---------------*---- 4 Ground *---- 9 Common RTS 7 -----[ 93.5K ohm ]----- 5 Low Battery or semi-conductor. Supported Models: Simple Signaling such as BackUPS This cable can only be used on voltage-signalling UPSes, and apparently only provides the On Battery signal. As a consequence, this cable is pretty much useless, and we recommend that you find a better cable because all APC UPSes support more than just On Battery.

Please note that we are not sure the following diagram is correct. This diagram is for informational purposes and may not be complete. We don't recommend that use it to build you build one yourself. APC Part# - 940-0023A Signal Computer UPS DB9F DB9M DCD 1 -------------------- 2 On Battery 3.3K ohm TxD 3 --[####]-* DTR 4 ---------* GND 5 ---------------*---- 4 Ground *---- 9 Common. Supported Models: APC BackUPS Pro PNP Contributed by: Chris Hanson cph at zurich.ai.mit.edu This is the definitive wiring diagram for the 940-0095A cable submitted by Chris Hanson, who disassembled the original cable, destroying it in the process. He then built one from his diagram and it works perfectly. APC Part# - 940-0095A UPS end Computer end ------- ------------ 47k 47k BATTERY-LOW (5) >----R1----*----R2----*--------------*----R4----*.

Supported Models: BackUPS XS1000(BX-1000), Possibly other USB models Contributed by: Jan Babinski jbabinsk at pulsarbeacon dot com 940-0128D is functionally similar to the 940-0128A cable except for NC on (6) DTR and (2) RD on the computer side. Unverified: Try setting apcupsd to UPSTYPE dumb and UPSCABLE 940-0128A. APC Part# - 940-0128D DB9(Computer) RJ45-10(UPS) (5) (1) ____________ ( o o o o o ) [ oooooooooo ] o o o o / [____________] (9) (6) (10) [_] (1) RI(9) --------- 2k 1N5819 +---vvvv---+--[>-------------------------------->(8)KillPwr GND(5)----------------------------(7)Signal GND (Shield)--------------------------(4)Chassis GND. Note: In a future release of apcupsd this procedure will be replaced by a daemon operation that can be performed on all types of UPS. This section does not apply to voltage-signalling or dumb UPSes such as the older BackUPS models. Smart UPSes internally compute the remaining runtime, and apcupsd uses the value supplied by the UPS. As the batteries age (after say two or three years), the runtime computation may no longer be accurate since the batteries no longer hold the same charge.

As a consequence, in the event of a power failure, the UPS and thus apcupsd can report a runtime of 5 minutes remaining when in fact only one minute remains. This can lead to a shutdown before you might expect it, because regardless of the runtime remaining that is reported, the UPS will always correctly detect low batteries and report it, thus causing apcupsd to correctly shutdown your computer. If you wish to have the UPS recalibrate the remaining runtime calculations, you can do so manually as the current version of apcupsd does not support this feature. To do so, • Shutdown apcupsd • contact your UPS directly using some terminal program such as minicom, tip, or cu with the settings 2400 8N1 (2400 baud, 8 bits, no parity, 1 stop bit). Be extremely careful what you send to your UPS as certain characters may cause it to power down or may even cause damage to the UPS.

Try sending an upper case Y to the UPS (without a return at the end). It should respond with SM. If this is not the case, read the chapter on testing. If you fat finger the Y and enter y instead, no cause for alarm, you will simply get the APC copyright notice. • when you are sure you are properly connected send an upper case D (no cr). This will put the UPS into calibration mode, and it will drain the battery down to 25% capacity (35% for a Matrix) at which point it will go back on the mains. In doing so, it will recompute the runtime calibration.

• If you wish to abort the calibration, enter a second D command. • When you are done, restart apcupsd.

In principle, you should be able to do this with the computer powered by the UPS, but if you wish to be completely safe, you should plug your computer into the wall prior to performing the runtime calibration. In that case, you will need to artificially load the UPS with light bulbs or other means. You should supply a load of about 30 to 35% but not more than 50%. You can determine the load by looking at the output of the apcaccess status command while apcupsd is running. You should not run the recalibration command more than once or twice per year as discharging these kinds of batteries tends to shorten their life span. In general, each of these directives is required (except that the DEVICE directive is ignored for UPSCABLE ether and not required for UPSCABLE usb).

UPSTYPE driver The name of a driver. Should be one of dumb, apcsmart, net, usb, pcnet, snmp, or test. This describes your interface type. The UPSTYPE directive can be defined during installation by using the --with-upstype= option of the configure program. UPSCABLE cable Defines the type of cable connecting the UPS to your computer. Possible generic choices for are: simple, smart, ether, usb Or a specific cable model number may be used: 940-0119A, 940-0127A, 940-0128A, 940-0020B, 940-0020C, 940-0023A, 940-0024B, 940-0024C, 940-1524C, 940-0024G, 940-0095A, 940-0095B, 940-0095C, M- The --with-upscable= option of configure can be used to set a default for this directive during the your build.

DEVICE device Specify which device is used for UPS communications. For serial ports, it is usually something like /dev/ttyS0. For USB ports, you may leave the name of the device blank (no specification) and apcupsd will automatically search the standard locations for the UPS.

Normally, the configure program will set an appropriate default value. You may also specify the --with-serial-dev= option of the configure program to set this directive at build time. If you have specified UPSTYPE net, then the device name to be specified consists of hostname:port where the hostname is the fully qualified name or IP address of the host (NIS server) and the port (optional) is the port to use to contact the server. If you specified UPSTYPE snmp, then the device name becomes hostname:vendor:community.

Please see the chapter in this manual for more details. POLLTIME time in seconds The interval, in seconds, at which apcupsd polls the UPS for status. This rate is automatically set to 1 second if the UPS goes on batteries and reset to your specified value when the mains power returns. This setting applies both to directly-attached UPSes ( UPSTYPE apcsmart, usb, dumb) and networked UPSes ( UPSTYPE net, snmp). Lowering this setting will improve apcupsd's responsiveness to certain events at the cost of higher CPU utilization. The default of 60 is appropriate for most situations.

This directive was formerly known as NETTIME. LOCKFILE path to lockfile This option tells apcupsd where to create a lockfile for the USB or serial port in the specified directory. This is important to keep two programs from reading or writing the port at the same time. Please note that although the directive name is LOCKFILE, you are actually specifying the lock file path. Apcupsd automatically appends the name of the device when creating the file.

On most systems, this directive is automatically set by the./configure program. You may also explicitly set it during the build process by using the --with-lock-dir= option of the configure program. None of these directives are required for proper operation of apcupsd. NETSERVER [on off] This configuration directive turns the network information server on or off.

If it is on, apcupsd will spawn a child process that serves STATUS and EVENTS information over the network. This information is currently used by the Web-based CGI programs. The default is on. This option is required to be turned on for net clients and apcaccess to function.

NISIP IP-address This directive specifies the IP address of the network interface on which the NIS server will listen for incoming connections. Default value is 0.0.0.0 which means the NIS will listen for connections on all network interfaces. If your machine has more than one interface, you can specify the IP of a single interface to limit connections to only that interface. Furthermore, you can specify the loopback address (127.0.0.1) to accept connections only from the local machine.

You may also use the --with-nisip= option of the configure program to set this directive during the build. NISPORT port This configuration directive specifies the port to be used by the apcupsd Network Information Server. The default is platform dependent, but typically 3551, which we have received from IANA as the official apcupsd networking port. This value should only be changed if it conflicts with an existing service in use on your network or if you are running multiple instances of apcupsd on the same machine.

EVENTSFILE filename If you want the apcupsd network information server to provide the last 10 events via the network, you must specify a file where apcupsd will save these events. The default is: /etc/apcupsd/apcupsd.events. Currently, apcupsd will save at most the last 50 events. Periodically (once an hour by default), apcupsd will check the size of this file. When more than 50 events are recorded, apcupsd will truncate the file to the most recent 10 events.

Consequently this file will not grow indefinitely. Although we do not recommend it, you may change these values by editing apcevents.c and changing the appropriate defines. Be aware that if you set these values to very large numbers, apcupsd may make excessive memory demands on the system during the data access and file truncation operations. This filename may also be specified at build time by using the --with-log-dir= option of the configure program.

In general, none of these directives are required. However, if you have a voltage-signalling (dumb) UPS with a cable that does not support the Low Battery signal, you must set the TIMEOUT directive to force a shutdown. BATTERYLEVEL percent of battery If BATTERYLEVEL is specified, during a power failure, apcupsd will halt the system when the remaining battery charge falls below the specified percentage. The default is 5 percent. This directive is ignored for dumb (voltage-signalling) UPSes.

To totally disable this counter, set BATTERYLEVEL -1 in your apcupsd.conf file. MINUTES battery runtime in minutes If MINUTES is specified, during a power failure, apcupsd will shutdown the system when the remaining runtime on batteries as internally calculated by the UPS falls below the time specified. The default is 3. This directive is ignored for dumb (voltage-signalling) UPSes. It should be noted that some UPSes report an incorrect value for remaining runtime when the battery is fully charged.

This can be checked by examining the TIMELEFT value as printed in the output of an ' apcaccess status' command. If the value is zero or otherwise unreasonable, your UPS is probably broken.

In this case, we recommend that you disable this timer by setting MINUTES -1 in your apcupsd.conf file. TIMEOUT time in seconds After a power failure, apcupsd will halt the system when TIMEOUT seconds have expired.

A value of zero disables this timer. Normally for all Smart UPS models and dumb UPSes with cables that support low battery detection, this should be zero so that the shutdown time will be determined by the battery level and/or remaining runtime (see above) or in the case of a voltage-signalling UPS, when the battery is exhausted. This command is required for dumb UPSes that do not provide a battery exhausted signal (only testing can determine this point). For more information, see the section of this manual. This timer can also be useful if you want some slave machines to shutdown before other machines to conserve battery power. It is also useful for testing apcupsd because you can force a rapid shutdown by setting a small value (e.g.

60) and pulling the plug to the UPS. TIMEOUT, BATTERYLEVEL, and MINUTES can be set together without problems. Apcupsd will react to the first case or test that is valid. Normally SmartUPS users will set TIMEOUT to zero so that the system is shutdown depending on the percentage battery charge remaining ( BATTERYLEVEL) or the remaining battery runtime ( MINUTES). ANNOY time in seconds Specify the time in seconds between messages requesting logged in users to get off the system during a power failure. This timer starts only when the UPS is running on batteries. The default is 300 seconds (5 minutes).

Apcupsd sends the annoy messages by invoking the apccontrol script with the annoyme argument. The default is to send a wall message on Unix systems and a popup message in Windows. The value of ANNOYDELAY must be greater than the value of ANNOY in order to receive annoy messages (this doesn't make sense, and means that the default values do not generate annoy messages: KES). Note that if NOLOGON disable is set, the annoy messages will also be disabled.

ANNOYDELAY time in seconds Specify delay time in seconds before apcupsd begins requesting logged in users to get off the system during a power failure. This timer starts only after the UPS is running on batteries. This timer is reset when the power returns. The default is 60 seconds. Thus, the first warning to log off the system occurs after 60 seconds on batteries, assuming that NOLOGON is not set to disable. NOLOGON disable timeout percent minutes always Specifies when apcupsd should prevent user logins The type specified allows you define the point when apcupsd will create the 'nologin' file and thus when user logins are prohibited. Once the 'nologin' file is created, normal users are prevented from logging in.

Control of when this file is created is important for allowing systems with big UPSes to run as normally until the system administrator determines the need for preventing user logins. The feature also allows the system administrator to hold the 'ANNOY' factor until the 'nologin' file is created. The default is always disable if no NOLOGON directive is specified. The 'nologin' file will be created in the directory specified by the NOLOGINDIR directive described below. As far as I can tell, the only useful types are disable and always since the difference in the time when the logout warning is given and shutdown occurs for the other types is very short (KES). Disable prevents apcupsd from creating the nologin file.

Consequently, any user can login during a power failure condition. Also, the ANNOY feature is disabled so users will not be warned to logoff the system. Timeout specifies that apcupsd should prohibit logins after the UPS is on batteries for 90% of the time specified on the TIMEOUT configuration directive.

Normally you don't want to specify a TIMEOUT value, so this option is probably not too useful (KES). Percent specifies that apcupsd should prohibit logins when the remaining battery charge percentage reaches 110% or less than the value specified on the BATTERYLEVEL configuration directive. Thus if the BATTERYLEVEL is specified as 15, apcupsd will prohibit logins when the battery charge drops below 16% (15% X 110% = 16%). Minutes specifies that apcupsd should prohibit logins when the remaining runtime in minutes reaches 110% or less than the value specified on the MINUTES configuration directive. Thus if MINUTES is set to 3, apcupsd will prohibit logins when the remaining runtime is less than 3 minutes (3 X 110% = 3). Always causes apcupsd to immediately prohibit logins when a power failure occurs. This will also enable the ANNOY feature.

NOLOGINDIR path to nologin dir This directive configures the directory into which apcupsd will write the nologin file, as described above for the NOLOGON directive. Normally, the configure program will set an appropriate default value for your platform, often /etc. You may also specify the --with-nologdir= option of the configure program to change the default at compile time.

KILLDELAY time in seconds If KILLDELAY is set, apcupsd will continue running after a shutdown has been requested, and after the specified time in seconds, apcupsd will attempt to shut off the UPS the power. This directive should normally be disabled by setting the value to zero, but on some systems such as Win32 systems apcupsd cannot regain control after a shutdown to force the UPS to shut off the power.

In this case, with proper consideration for the timing, the KILLDELAY directive can be useful. Please be aware, if you cause apcupsd to kill the power to your computer too early, the system and the disks may not have been properly prepared. In addition, apcupsd must continue running after the shutdown is requested, and on Unix systems, this is not normally the case as the system will terminate all processes during the shutdown. SCRIPTDIR path to apccontrol dir This option configures the directory in which apccontrol and other event scripts are located. Normally, the configure program will set an appropriate default value for your platform, often /etc/apcupsd. PWRFAILDIR path to powerfail dir When apcupsd shuts down your system, it creates a temporary 'flag file' which is used by the operating system halt scripts to know if this shutdown is due to a power failure.

This directive configures which directory the flag file will be written into. The chosen directory must be writable by the user apcupsd is running as (normally root) and must not be cleared or unmounted early in the shutdown sequence. Normally, the configure program will set an appropriate default value for your platform, often /etc/apcupsd. You may also specify the --with-pwrfaildir= option of the configure program to change the default at compile time. STATTIME time in seconds This directive supplies the time interval in seconds between writes to the STATUS file. If set to zero, the STATUS file will not be written. Please note that in a future version of apcupsd the STATUS file code will disappear since its functionality has been replaced by the Network Information Server and by apcaccess status, as a consequence, it is normally disabled by setting it to zero.

STATFILE file This directive specifies the file to be used when writing the STATUS information. The default is /etc/apcupsd/apcupsd.status.

DATATIME time in seconds This directives supplies the time interval in seconds between writes of PowerChute-like data information to the log file. See the section of this manual for additional details. FACILITY log-facility The FACILITY directive can be used to change the system logging class or facility. The default is DAEMON.

This parameter can be useful if you wish to direct the apcupsd system logging information to other than your system default files. See the section of this manual for additional details. The following directives apply to sharing an UPS using a ShareUPS hardware module.

Most users will not use this mode. UPSCLASS standalone shareslave sharemaster The default is standalone and should be used for all machines powered by the UPS and having a serial port or other direct connection to the UPS. This is the normal case. Use shareslave if and only if you are using a ShareUPS and connected to a BASIC Port with Simple Signal.

This code is not fully tested. Use sharemaster, if and only if you are using a ShareUPS and connected to the ADVANCED Port Smart Signal control. This code is not fully tested. UPSMODE disable share For normal standalone operations, you will set UPSMODE disable to indicate that you are disabling the ShareUPS support. Use share for two or seven additional simple signal ports on a SmartAccessories(tm) (internal/external box) for SmartUPSes. The share and sharenet code is not fully tested.

These directives have no effect on the operation of apcupsd but are reserved for use by apctest when bulk programming the values of the UPS EEPROM configuration variables in a Smart-UPS model. UPSNAME Name of UPS. Maximum of 8 characters. BATTDATE [ mm/dd/yy dd/mm/yy ] Last battery replacement date. Maximum of 8 characters. SENSITIVITY [ H M L ] H: High (most sensitive setting) M: Medium L: Low (least sensitive setting) WAKEUP [ 000 060 180 300 ] The time delay in seconds that the UPS waits after the return of utility power before 'waking up' and restoring power to the connected equipment.

SLEEP [ 020 180 300 600 ] The time delay in seconds for which the UPS waits or 'sleeps' after it receives a request to power off the connected system. LOTRANSFER Low line voltage causing transfer to battery power or activation of SmartBoost. Allowable values depend on the last letter of the firmware or APCMODEL. Typical values are: D 106 103 100 097 M 177 172 168 182 A 092 090 088 086 I 208 204 200 196 where D = domestic (USA), M = Canada, A = Asia and I = International.

HITRANSFER High line voltage causing transfer to battery power or activation of SmartTrim. Allowable values depend on the last letter of the firmware or APCMODEL. Typical values are: D 127 130 133 136 M 229 234 239 224 A 108 110 112 114 I 253 257 261 265 where D = domestic (USA), M = Canada, A = Asia and I = International. RETURNCHARGE [ 00 15 50 90 ] Percentage of battery charge needed for the UPS to restore power to the connected equipment. BEEPSTATE [ 0 T L N ] Alarm delay.

0: Zero delay after power fails. T: When power fails plus 30 seconds. L: When low battery occurs. LOWBATT Low battery warning occurs when the specified number of minutes remains before the UPS estimates battery power will be exhausted. There are four user-changeable settings: 2, 5, 7, or 10 minutes OUTPUTVOLTS UPS nominal output voltage when running on battery.

Allowable values depend on the last letter of the firmware or APCMODEL. Typical values are: D 115 M 208 A 100 I 230 240 220 225 where D = domestic (USA), M = Canada, A = Asia and I = International. SELFTEST [ 336 168 ON OFF ] Self test interval in hours (336 = 2 weeks, 168 = 1 week, ON = at power on, OFF = never). STATUS output is in ASCII format with a single data value or piece of information on each line output. Because not all UPSes supply the same information, the output varies based on the type of UPS that you are using. In general, if the information is not available for your UPS, the line will be missing entirely or the data portion of the output record will contain an N/A indicating that the information is not available. Status logging consists of periodically logging ALL available information concerning the UPS.

Since the volume of data is rather large (over 1000 bytes per status), the STATUS data is not automatically sent to the system log file. Instead, it is written as a series of data records in a specific file (normally /etc/apcupsd/apcupsd.status). After each write, the file is rewound so that the size of the file remains constant. The STATUS file is kept for backward compatibility and will be eliminated in a future version of apcupsd.

The preferred method for obtaining this information is from apcaccess or by using the CGI interface (see ). To make reading the status data reliable via a named pipe, the first record written contains a version number, the number of records that follow the first record, and the total number of bytes in those subsequent records. An actual example of such a status file (/etc/apcupsd/apcupsd.status) is shown below. Consequently, the first record always consists of 24 bytes (23 characters followed by a newline).

This record starts with APC and as indicated in the example is followed by 37 records consisting of 906 bytes. The last record begins with END APC and contains the date and time matching the DATE record. When this data is written to a file, it is written as two records, the first record, and all the other records together. In reading the file, it can be either be read a record at a time, or in one big read.

When this data is written to syslog(), it is written a record at a time. The first record is the first 24 bytes. By having the number of records and the size in the first record, the complete status can be reliably reassembled. The meaning of the above variables are: APC Header record indicating the STATUS format revision level, the number of records that follow the APC statement, and the number of bytes that follow the record. DATE The date and time that the information was last obtained from the UPS. HOSTNAME The name of the machine that collected the UPS data. UPSNAME The name of the UPS as stored in the EEPROM or in the UPSNAME directive in the configuration file.

VERSION The apcupsd release number, build date, and platform. CABLE The cable as specified in the configuration file ( UPSCABLE). MODEL The UPS model as derived from information from the UPS. UPSMODE The mode in which apcupsd is operating as specified in the configuration file ( UPSMODE) STARTTIME The time/date that apcupsd was started.

STATUS The current status of the UPS (ONLINE, ONBATT, etc.) LINEV The current line voltage as returned by the UPS. LOADPCT The percentage of load capacity as estimated by the UPS. BCHARGE The percentage charge on the batteries. TIMELEFT The remaining runtime left on batteries as estimated by the UPS.

MBATTCHG If the battery charge percentage (BCHARGE) drops below this value, apcupsd will shutdown your system. Value is set in the configuration file ( BATTERYLEVEL) MINTIMEL apcupsd will shutdown your system if the remaining runtime equals or is below this point. Value is set in the configuration file ( MINUTES) MAXTIME apcupsd will shutdown your system if the time on batteries exceeds this value. A value of zero disables the feature.

Value is set in the configuration file ( TIMEOUT) MAXLINEV The maximum line voltage since the UPS was started, as reported by the UPS MINLINEV The minimum line voltage since the UPS was started, as returned by the UPS OUTPUTV The voltage the UPS is supplying to your equipment SENSE The sensitivity level of the UPS to line voltage fluctuations. DWAKE The amount of time the UPS will wait before restoring power to your equipment after a power off condition when the power is restored. DSHUTD The grace delay that the UPS gives after receiving a power down command from apcupsd before it powers off your equipment. DLOWBATT The remaining runtime below which the UPS sends the low battery signal. At this point apcupsd will force an immediate emergency shutdown. LOTRANS The line voltage below which the UPS will switch to batteries. HITRANS The line voltage above which the UPS will switch to batteries.

RETPCT The percentage charge that the batteries must have after a power off condition before the UPS will restore power to your equipment. ITEMP Internal UPS temperature as supplied by the UPS. ALARMDEL The delay period for the UPS alarm. BATTV Battery voltage as supplied by the UPS.

LINEFREQ Line frequency in hertz as given by the UPS. LASTXFER The reason for the last transfer to batteries. NUMXFERS The number of transfers to batteries since apcupsd startup. XONBATT Time and date of last transfer to batteries, or N/A. TONBATT Time in seconds currently on batteries, or 0.

CUMONBATT Total (cumulative) time on batteries in seconds since apcupsd startup. XOFFBATT Time and date of last transfer from batteries, or N/A.

SELFTEST The results of the last self test, and may have the following values: • OK: self test indicates good battery • BT: self test failed due to insufficient battery capacity • NG: self test failed due to overload • NO: No results (i.e. No self test performed in the last 5 minutes) STESTI The interval in hours between automatic self tests. STATFLAG Status flag.

English version is given by STATUS. DIPSW The current dip switch settings on UPSes that have them. REG1 The value from the UPS fault register 1. REG2 The value from the UPS fault register 2. REG3 The value from the UPS fault register 3. MANDATE The date the UPS was manufactured. SERIALNO The UPS serial number.

BATTDATE The date that batteries were last replaced. NOMOUTV The output voltage that the UPS will attempt to supply when on battery power.

NOMINV The input voltage that the UPS is configured to expect. NOMBATTV The nominal battery voltage. NOMPOWER The maximum power in Watts that the UPS is designed to supply. HUMIDITY The humidity as measured by the UPS. AMBTEMP The ambient temperature as measured by the UPS. EXTBATTS The number of external batteries as defined by the user. A correct number here helps the UPS compute the remaining runtime more accurately.

BADBATTS The number of bad battery packs. FIRMWARE The firmware revision number as reported by the UPS.

APCMODEL The old APC model identification code. END APC The time and date that the STATUS record was written. If specified in the configuration file, the STATUS data will also be written to the system log file. Please note, that it would not normally be wise to write this data to a normal system log file as there is no mechanism in syslog() to rewind the file and hence the log file would quickly become enormous. However, in two cases, it can be very useful to use syslog() to write this information. The first case is to set up your syslog.conf file so that the data is written to a named pipe. In this case, normally not more than about 8192 bytes of data will be kept before it is discarded by the system.

The second case is to setup your syslog.conf file so that the status data is sent to another machine, which presumably then writes it to a named pipe. Consequently, with this mechanism, provides a simple means of networking apcupsd STATUS information. Although we mention system logging of STATUS information, we strongly recommend that you use apcaccess or the CGI interface to get this information. If you experienced so problems with the testing procedures, or if you are porting apcupsd to another system, or you are simply curious, you may want to know exactly what is going on during the shutdown process.

The shutdown sequence is as follows: • apcupsd detects that there is a power problem and it calls /etc/apcupsd/apccontrol powerout. By default this event does nothing, but it can be overridden to notify users, etc. • After the configured ONBATTERYDELAY, apcupsd calls /etc/apcupsd/apccontrol onbattery, which normally sends a message to all users informing them that the UPS is on batteries. • When one of the conditions listed below occurs, apcupsd issues a shutdown command by calling /etc/apcupsd/apccontrol doshutdown, which should perform a shutdown of your system using the system shutdown(8) command.

You can modify the behavior as described in. The conditions that trigger the shutdown can be any of the following: • Running time on batteries have expired ( TIMEOUT) • The battery runtime remaining is below the configured value ( BATTERYLEVEL) • The estimated remaining runtime is below the configured value ( MINUTES) • The UPS signals that the batteries are exhausted. A shutdown could also be initiated if apcupsd detects that the batteries are no longer functioning correctly. This case, though very unusual, can happen at any time even if there is proper mains voltage, and /etc/apcupsd/apccontrol emergency is called. Just before initiating any shutdown through the apccontrol script, apcupsd will create the file /etc/apcupsd/powerfail. This file will be used later in the shutdown sequence to recall apcupsd after syncing of the disks to initiate a power off of the UPS. If the /etc/nologin file has not already been created, it will normally be created during the shutdown sequence to prevent additional users from logging in (see the NOLOGIN configuration directive).

Even though apcupsd has requested the system to perform a shutdown, it continues running. • When the system signals apcupsd to do exit, it does so.

This is part of the normal system shutdown (at least on Unix and Linux systems) and the exact time that apcupsd receives the termination signal depends on how the shutdown links (usually in /etc/rc.d) are set. Note that on Windows NT systems, apcupsd apparently continues to run as a Service even though the machine is 'shutdown'. • During the shutdown of the system after apcupsd has been forced to exit, one of the last things done by the system shutdown is to call the halt script, which is usually in /etc/rc.d/halt or /etc/rc.d/init.d/halt, or possibly in /sbin/init.d/rc.0 depending on your system.

If apcupsd was properly installed, this standard halt script was modified to include a bit of new logic just before the final halt of the system. It first tests if the file /etc/apcupsd/powerfail exists, and if it does, it executes /etc/apcupsd/apccontrol killpower.

It is this last step that will cause apcupsd to be re-executed with the --killpower option on the command line. This option tells apcupsd to inform the UPS to kill the power. This final step is important if you want to ensure that your system will automatically reboot when the power comes back on. The actual code used on the Red Hat version is: # See if this is a powerfail situation. # ***apcupsd*** if [ -f /etc/apcupsd/powerfail ]; then # ***apcupsd*** echo # ***apcupsd*** echo 'APCUPSD will now power off the UPS' # ***apcupsd*** echo # ***apcupsd*** /etc/apcupsd/apccontrol killpower # ***apcupsd*** echo # ***apcupsd*** echo 'Please ensure that the UPS has powered off before rebooting' # ***apcupsd*** echo 'Otherwise, the UPS may cut the power during the reboot!!!'

# ***apcupsd*** echo # ***apcupsd*** fi # ***apcupsd*** The above code must be inserted as late as possible in the halt script. On many systems, such as Red Hat, all the disk drives were unmounted, then remounted read-only, thus permitting access to the /etc files and the apcupsd executable. If your system does not explicitly remount the disks, you must remount them in read-only mode in the code that you add.

Examples of code fragments that do this can be found in the distributions/suse subdirectory of the source. If you are not able to insert the above code in your halt script because there is no halt script, or because your halt script calls the init program as some Unix systems do, you can either just forget about powering off the UPS, which means that your machine will not automatically reboot after a power failure, or there is yet another alternative, though not at all as satisfying as inserting code in the halt script. Only if you cannot insert the appropriate code in the halt script, when you start apcupsd, normally from the /etc/rc.d/init.d/apcupsd script, use the --kill-on-powerfail option. This will cause apcupsd to program the UPS to shutoff the power just before it (apcupsd) does the system shutdown. Please note that this is not the most ideal solution. Read on to understand why. A very important consideration is that you must set the EEPROM in your UPS so that it waits a sufficient time for the system to halt before it shuts off the UPS power.

When using a USB connection, apcupsd automatically sets this value to 60 seconds. When using a serial connection to a SmartUPS, you must configure the value in the UPS EEPROM by hand using apctest. In master/slave configurations, however, the master cannot be 100 percent sure that the slaves have all shutdown before it performs the power off.

To avoid this situation, be sure to configure any slaves (clients) to shut down before the master by setting different TIMEOUT, BATTERYLEVEL, or MINUTES parameters in the config file. Also, on a slave machine, you do not want to use the modified halt script since it will recall apcupsd, which will detect that it is a slave (i.e. No connection to the UPS) and will complain that it cannot do the killpower. This situation is not harmful just annoying and possibly confusing. One possible problem during shutdown can be caused by remnants of old versions. Please be sure to delete or rename all prior versions (/usr/local/sbin/apcupsd or /sbin/powersc). Normally, apcupsd is automatically started when your system is rebooted.

This normally occurs because the startup script apcupsd is linked into the appropriate places in /etc/rc.d. On most Linux systems, there is a program called chkconfig(8) that will automatically link the startup script. This program is invoked by the make install scripts, or it is explicitly done for those systems that do not have chkconfig(8). If this is not the case, you can either link it in appropriately yourself or explicitly call it from your rc.local file. The appropriate manual way to startup apcupsd is by executing: /apcupsd start where path is normally /etc/rc.d or /etc/rc.d/init.d depending on your system. Using this script is important so that any files remaining around after a power failure are removed. Likewise, shutting down apcupsd should be done with the same script: /apcupsd stop.

The APC UPS protocol was originally analyzed by Pavel Korensky with additions from Andre H. Hendrick beginning in 1995, and we want to give credit for good, hard work, where credit is due. After having said that, you will see that Steven Freed built much of the original apcupsd information file. The start of this chapter of the apcupsd manual in HTML format was pulled from the Network UPS Tools (NUT) site (). It has been an invaluable tool in improving apcupsd, and I consider it the Bible of APC UPS programming. In the course of using it, I have added information gleaned from apcupsd and information graciously supplied by APC.

This is probably the most important register of the UPS, which indicates the overall UPS status. Some common things you'll see: • 08 = On line, battery OK • 10 = On battery, battery OK • 50 = On battery, battery low • SM = Status bit is still not available (retry reading) Bit Meaning when bit=1 0 Runtime calibration occurring (Not reported by Smart UPS v/s and BackUPS Pro) 1 SmartTrim (Not reported by 1st and 2nd generation SmartUPS models) 2 SmartBoost 3 On line (this is the normal condition) 4 On battery 5 Overloaded output 6 Battery low 7 Replace battery. These single character messages are sent by the UPS any time there is an Alert condition.

All other responses indicated above are sent by the UPS only in response to a query or action command. Character Meaning Description!

Line Fail Sent when the UPS goes on-battery, repeated every 30 seconds until low battery condition reached. Sometimes occurs more than once in the first 30 seconds. $ Return from line fail UPS back on line power. Only sent if a!

Has been sent previously.% Low battery Sent to indicate low battery. Not implemented on SmartUPS v/s or BackUPS Pro models + Return from low batt Sent when the battery has been recharged to some level Only sent if a% has been sent previously.?

Abnormal condition Sent for conditions such as 'shutdown due to overload' or 'shutdown due to low battery capacity'. Also occurs within 10 minutes of turnon. = Return from abnormal condition Sent when the UPS returns from an abnormal condition where? Was sent, but not a turn-on.

Not implemented on SmartUPS v/s or BackUPS Pro models. * About to turn off Sent when the UPS is about to switch off the load. No commands are processed after this character is sent. Not implemented on SmartUPS v/s, BackUPS Pro, or 3rd generation SmartUPS models. # Replace battery Sent when the UPS detects that the battery needs to be replaced.

Sent every 5 hours until a new battery test is run or the UPS is shut off. Not implemented on SmartUPS v/s or BackUPS Pro models.

& Check alarm register for fault (Measure-UPS) Sent to signal that temp or humidity out of set limits. Also sent when one of the contact closures changes state. Sent every 2 minutes until the alarm conditions are reset. Only sent for alarms enabled with I. Cause of alarm may be determined with J. Not implemented on SmartUPS v/s or BackUPS Pro. Variable change in EEPROM Sent whenever any EEPROM variable is changed. Only supported on Matrix UPS and 3rd generation SmartUPS models.

All bits are valid on the Matrix UPS and 3rd generation SmartUPS models. SmartUPS v/s and BackUPS Pro models report bits 0-5. All others report 0-4.

State change of bits 1,2,5,6,7 are reported asynchronously with? And = messages. Bit Meaning when bit=1 0 Output unpowered due to shutdown by low battery 1 Unable to transfer to battery due to overload 2 Main relay malfunction - UPS turned off 3 In sleep mode from @ command (maybe others) 4 In shutdown mode from S command 5 Battery charger failure 6 Bypass relay malfunction 7 Normal operating temperature exceeded. The Old Firmware Revision is obtained with the 'V' command, which gives a typical response such as 'GWD' or 'IWI', and can be interpreted as follows: Old Firmware revision and model ID String for SmartUPS & MatrixUPS This is a three character string XYZ where X == Smart-UPS or Matrix-UPS ID Code. Range 0-9 and A-P 1 == unknown 0 == Matrix 3000 5 == Matrix 5000 the rest are Smart-UPS and Smart-UPS-XL 2 == 250 3 == 400 4 == 400 6 == 600 7 == 900 8 == 1250 9 == 2000 A == 1400 B == 1000 C == 650 D == 420 E == 280 F == 450 G == 700 H == 700XL I == 1000 J == 1000XL K == 1400 L == 1400XL M == 2200 N == 2200XL O == 3000 P == 5000 where Y == Possible Level of Smart Features, unknown??? G == Stand Alone T == Stand Alone V ==??? W == Rack Mount where Z == National Model Use Only Codes D == Domestic 115 Volts I == International 230 Volts A == Asia??

100 Volts J == Japan?? New Firmware revision and model ID String in NN.M.L is the format where NN == UPS ID Code. 12 == Back-UPS Pro 650 13 == Back-UPS Pro 1000 52 == Smart-UPS 700 60 == SmartUPS 1000 72 == Smart-UPS 1400 where NN now Nn has possible meanings. N == Class of UPS 1n == Back-UPS Pro 5n == Smart-UPS 7n == Smart-UPS NET n == Level of intelligence N1 == Simple Signal, if detectable WAG(*) N2 == Full Set of Smart Signals N3 == Micro Subset of Smart Signals where M == Possible Level of Smart Features, unknown??? 1 == Stand Alone 8 == Rack Mount 9 == Rack Mount where L == National Model Use Only Codes D == Domestic 115 Volts I == International 230 Volts A == Asia??

100 Volts J == Japan?? 100 Volts M == North America 208 Volts (Servers). Upon sending a ^Z, your UPS will probably spit back approximately 254 characters something like the following (truncated here for the example): #uD8129uM9224uA4108.

It looks bizarre and ugly, but is easily parsed. The # is some kind of marker/ident character. The rest fits this form: • Command character - use this to select the value • Locale - use 'b' to find out what yours is (the last character), '4' applies to all • Number of choices - '4' means there are 4 possibilities coming up • Choice length - '3' means they are all 3 chars long Then it's followed by the choices, and it starts over. Matrix-UPS models have ## between each grouping for some reason. Here is an example broken out to be more readable: CMD DFO RSP FSZ FVL u D 4 3 127 130 133 136 u M 4 3 229 234 239 224 u A 4 3 108 110 112 114 u I 4 3 253 257 261 265 l D 4 3 106 103 100 097 l M 4 3 177 172 168 182 l A 4 3 092 090 088 086 l I 4 3 208 204 200 196 e 4 4 2 00 15 50 90 o D 1 3 115 o J 1 3 100 o I 1 3 230 240 220 225 o M 1 3 208 s 4 4 1 H M L L q 4 4 2 02 05 07 10 p 4 4 3 020 180 300 600 k 4 4 1 0 T L N r 4 4 3 000 060 180 300 E 4 4 3 336 168 ON OFF CMD == UPSlink Command.